Installation
2–14 975-0082-01-01
Type 5
Type 5 is a three-wire StartStop configuration that uses relay 3 to provide
the preheat signal for Generac’s Guardian Diesel generators.
The wiring diagram for a Type 5 configuration is the same as a Type 4
(see Figure 2-6).
Table 2-6
Type 5 relay and timing preset configurations
Relay 1 mode StartStop
Relay 3 mode Preheat
Gen Run signal hold time 2 s
Preheat time 15 s
Preheat to crank delay 2 s
Crank time 15 s
Crank retry time 15 s
Shutdown bypass time 0 s
Start tries 3