The Auto Gen Start Menu
975-0082-01-01 3–33
Crank Retry Time
Purpose “Crank Retry Time” specifies the length of time the Start relay is engaged
(and cranking the starter motor) for the second and subsequent attempts to
start the generator, in cases when the generator fails to start on the first
attempt.
When to use This setting is automatically configured when you select a “Gen Type” for
your generator. You should manu ally set “Crank Retry Time” if you need
to customize your Gen Type on the advice of your generator manufacturer
or authorized service personnel.
Preheat Time
Purpose “Preheat Time” specifies how long the Preheat relay is engaged during the
start sequence. The preheat signal may be required for diesel generators
with glow plugs or fuel priming for gas generators.
The Preheat relay may be Relay 1 or Relay 3, depending on the “Relay3”
setting or the Gen Type selected.
When to use This setting is automatically configured when you select a “Gen Type” for
your generator. You should manually set “Preheat Time” if you need to
customize your Gen Type on the advice of your generator manufacturer or
authorized service personnel.
Valu es Def aul t
0s to 250s (increments of 1s) 40s
Valu es Def aul t
0s to 250s (increments of 1s) 0s