1. FLUE OUTLET POSITIONS

SITE REQUIREMENTS

1. FLUE OUTLET POSITIONS

Terminal

Flue

Vertical

Measurement

Horizontal

Measurement

150mm

max

Adjacent

Building

Insulation

The vertical measurement is the lowest from either the point of discharge or 150mm above insulation.

IMPORTANT: Seek specialist advice if installing in a dwelling with a thatched roof

 

Position On Roof

Minimum Clearances

 

 

 

A

On ridge or within 600mm

600mm above ridge

B

Elsewhere on roof

2300mm horizontally from roof surface and:

 

 

a) 1000mm above highest point of flue exit

 

 

from roof or

 

 

b) as high as the ridge

 

 

 

C

On pitched, within 2300mm horizontally to

1000mm above top of opening

 

openable window, dormer

 

D

Within 2300mm of another building

600mm above top of building

1. HEARTH DIMENSIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150mm

 

 

 

 

 

 

 

 

150mm

 

 

 

 

 

 

 

150mm

 

 

 

minimum

 

 

 

 

 

 

minimum

 

 

 

 

225mm

 

 

 

 

 

 

 

minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

minimum

Constructional

 

Hearth

 

 

 

 

 

 

 

 

 

 

 

Constructional Hearth

 

 

 

840mm minimum

 

 

840mm minimum

 

 

 

 

 

 

 

PR8730

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.1The appliance must stand on a non-combustible constructional hearth which is at least 125mm thick with the minimum dimensions as shown in diagram.

2.2If this appliance can be installed in an elevated setting it is recommended to increase the 225mm hearth depth to safely contain any falling logs or embers. The higher the appliance is installed the deeper the hearth should be to avoid scorched floor coverings.

2.3The building must have a suitable load-bearing capacity for the hearth and appliance. Consult a structural engineer for advice before proceeding.

2.4When fitting into an existing hearth check that the hearth complies with current construction regulations and is at least the minimum sizes shown.

2.5If there is no existing fireplace or chimney it is possible to construct a suitable non-combustible housing and hearth setting. The flue must be installed in accordance with all local and national regulations and current rules in force.

Check if adding a new chimney to your property requires planning permission.