Before lifting, make sure the unit weight is distrib- uted equally on the rigging cables so it will lift evenly.

Units may be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose.

LENGTH OF FORKS MUST BE A MINIMUM OF 60 INCHES.

All panels must be secured in place when the unit is lifted.

The condenser coils should be protected from rig- ging cable damage with plywood or other suitable material.

TABLE 4: 6 POINT LOAD WEIGHT

Model

 

 

Location (lbs.)*

 

 

 

 

 

 

 

 

 

A

B

C

D

E

F

 

 

 

 

 

 

 

DM090

158

142

128

187

207

230

 

 

 

 

 

 

 

DM120

168

151

136

198

219

244

 

 

 

 

 

 

 

DM150

180

161

145

212

235

262

 

 

 

 

 

 

 

*. Weights include largest gas heat option.

TABLE 5: 4 POINT LOAD WEIGHT

Model

 

Location (lbs.)*

 

 

 

 

 

 

A

B

C

D

 

 

 

 

 

DM090

230

197

287

336

 

 

 

 

 

DM120

245

209

305

357

 

 

 

 

 

DM150

262

224

327

382

 

 

 

 

 

*. Weights include largest gas heat option.

LEFT

FRONT

BC

LEFT

A

FRONT

CD

B

E

F

A

FIGURE 6 - UNIT 6 POINT LOAD

D

FIGURE 5 - UNIT 4 POINT LOAD

TABLE 3:

UNIT WEIGHTS

 

Model

Shipping Weight* (lb.)

Operating Weight(lb.)

DM090

1056

1051

 

 

 

DM120

1121

1116

 

 

 

DM150

1200

1195

 

 

 

Econ.

85

84

 

 

 

w/ PE

150

148

 

 

 

Elec. Heat2

49

49

*. Weights include largest gas heat option.

†.54kW heater.

LEFT471/2"

251/2"FRONT

FIGURE 7 - UNIT CENTER OF GRAVITY CLEARANCES

All units require particular clearances for proper operation and service. Installer must make provisions for adequate ventilation air in accordance with applicable provisions of the local building codes. Refer to Table 6 for clearances required for combustible construction, servicing, and proper unit oper- ation.

12

Unitary Products Group

Page 12
Image 12