York 150, 120 installation manual 035-17311-002-A-0803

Models: 120 150

1 44
Download 44 pages 20.16 Kb
Page 38
Image 38
Manual background

035-17311-002-A-0803

TABLE 35: 10 TON STANDARD EFFICIENCY SUPERHEAT CHARGING

 

 

 

 

 

Superheat at Compressor Suction (°F)

 

 

 

 

Outdoor

 

 

 

 

 

Airflow = 4000 CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (°F)

 

 

 

 

 

Indoor WB Temp (°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

19.6

20.8

22.0

23.2

 

24.4

25.6

26.9

 

28.4

29.9

31.4

32.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

14.4

16.0

17.5

19.0

 

20.5

22.0

23.5

 

25.4

27.3

29.2

31.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

9.3

11.1

12.9

14.7

 

16.6

18.4

20.2

 

22.4

24.7

26.9

29.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

-

6.3

8.4

10.5

 

12.6

14.8

16.9

 

19.5

22.0

24.6

27.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

-

-

-

6.3

 

8.7

11.1

13.6

 

16.5

19.4

22.4

25.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90

-

-

-

5.6

 

7.8

9.9

12.0

 

15.0

17.9

20.8

23.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95

-

-

-

-

 

6.8

8.7

10.5

 

13.4

16.3

19.3

22.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

-

-

-

-

 

5.3

6.7

8.1

 

10.8

13.5

16.2

18.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

105

-

-

-

-

 

-

-

5.7

 

8.1

10.6

13.1

15.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

110

-

-

-

-

 

-

-

-

 

5.5

7.7

10.0

12.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115

-

-

-

-

 

-

-

-

 

-

-

6.9

8.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 36: 12.5 TON STANDARD EFFICIENCY SUPERHEAT CHARGING

 

 

 

 

 

Superheat at Compressor Suction (°F)

 

 

 

 

Outdoor

 

 

 

 

 

Airflow = 5000 CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp (°F)

 

 

 

 

 

Indoor WB Temp (°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

57

59

61

 

63

65

67

 

69

71

73

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

33.6

34.2

34.7

35.3

 

35.9

36.4

37.0

 

37.3

37.5

37.8

38.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

29.6

30.4

31.1

31.9

 

32.7

33.4

34.2

 

34.7

35.3

35.8

36.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

25.6

26.6

27.5

28.5

 

29.5

30.5

31.4

 

32.2

33.0

33.8

34.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

21.6

22.8

24.0

25.1

 

26.3

27.5

28.6

 

29.7

30.8

31.8

32.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

17.6

19.0

20.4

21.7

 

23.1

24.5

25.9

 

27.2

28.5

29.9

31.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90

11.6

13.4

15.2

16.9

 

18.7

20.5

22.3

 

24.3

26.3

28.3

30.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95

5.6

7.8

10.0

12.1

 

14.3

16.5

18.7

 

21.3

24.0

26.7

29.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

-

6.1

7.8

9.4

 

11.1

12.8

14.5

 

17.5

20.6

23.7

26.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

105

-

-

5.5

6.7

 

7.9

9.1

10.3

 

13.8

17.2

20.7

24.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

110

-

-

-

-

 

-

5.4

6.1

 

10.0

13.8

17.6

21.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115

-

-

-

-

 

-

-

-

 

6.2

10.4

14.6

18.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38

Unitary Products Group

Page 38
Image 38
York 150, 120 installation manual 035-17311-002-A-0803