TABLE 23: 7-1/2 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE* †

 

 

 

 

 

 

 

 

 

TURNS OPEN**

 

 

 

 

 

 

 

 

ESP

 

0

 

 

1

 

 

2

 

 

 

3

 

 

4

 

 

5

 

 

CFM

W††

BHP

CFM

W††

BHP

CFM

W††

 

BHP

CFM

W††

BHP

CFM

W††

BHP

CFM

W††

BHP

0.4

-

-

-

-

-

-

3736

1476

 

1.58

3487

1284

1.38

3231

1109

1.19

3001

970

1.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

-

-

-

3572

1514

1.62

3389

1339

 

1.44

3094

1151

1.23

2764

972

1.04

2446

824

0.88

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

3422

1558

1.67

3179

1364

1.46

2889

1164

 

1.25

2554

985

1.06

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

2891

1347

1.44

2372

1088

1.17

2050

922

 

0.99

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2

2017

1051

1.13

-

-

-

-

-

 

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*. Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.

†.Blower performance includes two-inch throwaway filters.

‡.ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the total static pressure of the blower.

**. “Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.

††.W = Watts

TABLE 24: 7-1/2 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE* †

 

 

 

 

 

 

 

 

 

TURNS OPEN**

 

 

 

 

 

 

 

 

ESP

 

0

 

 

1

 

 

2

 

 

 

 

3

 

 

4

 

 

5

 

 

CFM

W††

BHP

CFM

W††

BHP

CFM

W††

 

BHP

CFM

 

W††

BHP

CFM

W††

BHP

CFM

W††

BHP

0.4

-

-

-

-

-

-

-

-

 

-

-

 

-

-

-

-

-

3910

1726

1.85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

-

-

-

-

-

-

-

-

 

-

-

 

-

-

3857

1842

1.98

3597

1430

1.53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

-

-

-

-

-

-

-

-

 

-

3804

 

1957

2.10

3503

1689

1.81

3172

1430

1.53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

-

-

-

-

-

-

3774

2088

 

2.24

3406

 

1778

1.91

3032

1497

1.61

2248

1143

1.23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2

-

-

-

-

-

-

3327

1866

 

2.00

2926

 

1578

1.69

2160

1217

1.31

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4

-

-

-

3270

1971

2.11

2537

1544

 

1.66

2043

 

1296

1.39

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.6

3196

2077

2.23

2460

1651

1.77

-

-

 

-

-

 

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.8

2426

1768

1.90

-

-

-

-

-

 

-

-

 

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*. Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.

†.Blower performance includes two-inch throwaway filters.

‡.ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the total static pressure of the blower.

**. “Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.

††.W = Watts