TABLE 9: ELECTRICAL DATA - BCH036 - 060 DIRECT DRIVE (CONT.)
|
| COMPRESSORS | OD FAN | ID |
|
|
| MIN. | MAX. FUSE/ | |
MODEL | VOLTAGE | RLA | LRA | BLOWER | ELECTRIC HEATER | HEATER | HEATER | CIRCUIT | BRKR1 | |
MOTOR | MOTOR | MODEL NO. | KW | AMPS | AMPACITY | SIZE | ||||
|
| EACH | EACH | FLA | ||||||
|
| FLA |
|
|
| (AMPS) | (AMPS) | |||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| None | 33.0 | 45 | ||
|
|
|
|
|
| 2CE045105252 | 4.0 | 11.1 | 46.9 | 60 |
| 19.3 | 137.0 | 2.3 | 6.6 | 2CE045107252 | 5.6 | 15.5 | 52.5 | 60 | |
| 2CE04511025 | 8.0 | 22.2 | 60.8 | 70 | |||||
|
|
|
|
|
| 2CE04511525 | 11.9 | 33.0 | 74.3 | 80 |
|
|
|
|
|
| 2CE04512025 | 15.9 | 44.1 | 88.2 | 90 |
|
|
|
|
|
| 2CE04513025 | 22.2 | 61.6 | 110.1 | 125 |
|
|
|
|
|
| None | 33.0 | 45 | ||
|
|
|
|
|
| 2CE045105252 | 5.3 | 12.7 | 49.0 | 60 |
| 19.3 | 137.0 | 2.3 | 6.6 | 2CE045107252 | 7.5 | 18.0 | 55.6 | 70 | |
| 2CE04511025 | 10.6 | 25.5 | 64.9 | 70 | |||||
BCH060 |
|
|
|
|
| 2CE04511525 | 15.9 | 38.2 | 80.8 | 90 |
|
|
|
|
| 2CE04512025 | 21.2 | 51.0 | 96.8 | 100 | |
|
|
|
|
|
| 2CE04513025 | 29.6 | 71.2 | 122.0 | 125 |
|
|
|
|
|
| None | 17.1 | 25 | ||
|
|
|
|
|
| 2CE045107462 | 6.8 | 8.2 | 27.3 | 35 |
| 10.0 | 62.0 | 1.3 | 3.3 | 2CE045110462 | 10.1 | 12.1 | 32.3 | 35 | |
| 2CE045115462 | 13.6 | 16.4 | 37.5 | 40 | |||||
|
|
|
|
|
| |||||
|
|
|
|
|
| 2CE045120462 | 19.5 | 23.5 | 46.4 | 50 |
|
|
|
|
|
| 2CE045130462 | 28.8 | 34.6 | 60.4 | 70 |
|
|
|
|
|
| None | 13.5 | 20 | ||
| 7.9 | 50.0 | 1.3 | 3.3 | 2CE04511058 | 10.6 | 10.2 | 26.2 | 30 | |
| 2CE04511558 | 15.9 | 15.3 | 32.6 | 35 | |||||
|
|
|
|
|
| 2CE04512058 | 21.2 | 20.4 | 39.0 | 40 |
|
|
|
|
|
| 2CE04513058 | 30.4 | 29.3 | 50.1 | 60 |
1.HACR Type per NEC.
2.These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
16 | Unitary Products Group |