177820-YIM-A-0506

TABLE 9: ELECTRICAL DATA - BCH036 - 060 DIRECT DRIVE (CONT.)

 

 

COMPRESSORS

OD FAN

ID

 

 

 

MIN.

MAX. FUSE/

MODEL

VOLTAGE

RLA

LRA

BLOWER

ELECTRIC HEATER

HEATER

HEATER

CIRCUIT

BRKR1

MOTOR

MOTOR

MODEL NO.

KW

AMPS

AMPACITY

SIZE

 

 

EACH

EACH

FLA

 

 

FLA

 

 

 

(AMPS)

(AMPS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

33.0

45

 

 

 

 

 

 

2CE045105252

4.0

11.1

46.9

60

 

208-3-60

19.3

137.0

2.3

6.6

2CE045107252

5.6

15.5

52.5

60

 

2CE04511025

8.0

22.2

60.8

70

 

 

 

 

 

 

2CE04511525

11.9

33.0

74.3

80

 

 

 

 

 

 

2CE04512025

15.9

44.1

88.2

90

 

 

 

 

 

 

2CE04513025

22.2

61.6

110.1

125

 

 

 

 

 

 

None

--

--

33.0

45

 

 

 

 

 

 

2CE045105252

5.3

12.7

49.0

60

 

230-3-60

19.3

137.0

2.3

6.6

2CE045107252

7.5

18.0

55.6

70

 

2CE04511025

10.6

25.5

64.9

70

BCH060

 

 

 

 

 

2CE04511525

15.9

38.2

80.8

90

 

 

 

 

 

2CE04512025

21.2

51.0

96.8

100

 

 

 

 

 

 

2CE04513025

29.6

71.2

122.0

125

 

 

 

 

 

 

None

--

--

17.1

25

 

 

 

 

 

 

2CE045107462

6.8

8.2

27.3

35

 

460-3-60

10.0

62.0

1.3

3.3

2CE045110462

10.1

12.1

32.3

35

 

2CE045115462

13.6

16.4

37.5

40

 

 

 

 

 

 

 

 

 

 

 

 

2CE045120462

19.5

23.5

46.4

50

 

 

 

 

 

 

2CE045130462

28.8

34.6

60.4

70

 

 

 

 

 

 

None

--

--

13.5

20

 

575-3-60

7.9

50.0

1.3

3.3

2CE04511058

10.6

10.2

26.2

30

 

2CE04511558

15.9

15.3

32.6

35

 

 

 

 

 

 

2CE04512058

21.2

20.4

39.0

40

 

 

 

 

 

 

2CE04513058

30.4

29.3

50.1

60

1.HACR Type per NEC.

2.These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.

16