TABLE 19: BELT DRIVE BLOWER MOTOR AND DRIVE DATA

177820-YIM-A-0506

TABLE 18: SUPPLY AIR BLOWER PERFORMANCE (3 - 5 TON DIRECT DRIVE) - SIDE DUCT APPLICATION

UNIT

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE-IWG2

 

 

 

MOTOR SPEED

 

0.20

 

0.30

 

0.40

 

 

0.50

 

0.60

TONNAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

 

CFM

 

WATTS

CFM

 

WATTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HI

-

 

-

-

 

-

-

 

-

 

1720

 

825

1665

 

795

31

MED

1660

 

850

1630

 

820

1590

 

780

 

1550

 

750

1500

 

720

 

LOW

1470

 

750

1440

 

725

1410

 

700

 

1370

 

675

1330

 

650

 

HI

-

 

-

-

 

-

2000

 

1010

 

1950

 

975

1905

 

945

41

MED

1810

 

910

1780

 

880

1740

 

850

 

1700

 

825

1665

 

800

 

LOW

1635

 

810

1610

 

780

1580

 

760

 

1555

 

740

1540

 

730

 

HI

-

 

-

-

 

-

2500

 

1400

 

2420

 

1350

2340

 

1300

51

MED

2390

 

1350

2350

 

1300

2300

 

1255

 

2245

 

1210

2190

 

1165

 

LOW

2270

 

1320

2230

 

1270

2190

 

1220

 

2145

 

1170

2090

 

1110

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE-IWG2

 

 

 

 

 

 

MOTOR SPEED

 

0.70

 

0.80

 

0.90

 

 

1.00

 

 

 

TONNAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

WATTS

CFM

 

WATTS

CFM

 

WATTS

 

CFM

 

WATTS

 

 

 

 

HI

1600

 

765

1540

 

735

1490

 

700

 

1380

 

670

 

 

 

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MED

1450

 

690

1400

 

665

1360

 

650

 

1270

 

610

 

 

 

 

LOW

1290

 

625

1250

 

610

1220

 

600

 

1130

 

560

 

 

 

 

HI

1840

 

910

1770

 

825

1660

 

825

 

1530

 

775

 

 

 

41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MED

1620

 

775

1560

 

740

1480

 

700

 

1390

 

660

 

 

 

 

LOW

1510

 

715

1460

 

690

1400

 

660

 

1300

 

615

 

 

 

 

HI

2260

 

1250

2160

 

1190

2060

 

1135

 

1925

 

1065

 

 

 

51

MED

2130

 

1120

2065

 

1075

1990

 

1030

 

1900

 

970

 

 

 

 

LOW

2030

 

1070

1960

 

1020

1890

 

970

 

1810

 

920

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Side Duct application (230/460/575 Volts)

2.Includes allowances for a wet evaporator coil and 1” filters. Refer to STATIC RESISTANCES Table for resistance values.

TABLE 19: BELT DRIVE BLOWER MOTOR AND DRIVE DATA

 

 

MOTOR1

ADJUSTABLE MOTOR PULLEY

 

FIXED BLOWER PULLEY

 

 

BELT

 

MODEL

BLOWER

 

 

(NOTCHED)

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

 

 

DESIG-

OUTSIDE

PITCH

 

BORE

DESIG-

OUTSIDE

PITCH

 

BORE

DESIG-

PITCH

 

(RPM)

HP

FRAME

DIA.

DIA.

 

DIA.

DIA.

 

LENGTH

QTY.

 

NATION

 

(IN.)

NATION

 

(IN.)

NATION

 

 

 

 

 

 

 

 

 

(IN.)

(IN.)

 

 

 

(IN.)

(IN.)

 

 

 

(IN.)

 

3 TON

790/1120

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

 

5/8

AK61

5.9

5.7

 

1

A36

37.3

1

4 TON

790/1120

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

 

5/8

AK61

5.9

5.7

 

1

A36

37.3

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 TON

850/1220

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

 

5/8

AK56

5.4

5.2

 

1

A36

37.3

1

1.All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.

Unitary Products Group

25

Page 25
Image 25
York 048 & 060, BCH 036 installation manual Belt Drive Blower Motor And Drive Data, YIM-A-0506, Unitary Products Group