TABLE 3: ELECTRIC HEATER CFM LIMITATIONS

177820-YIM-A-0506

TABLE 3: ELECTRIC HEATER CFM LIMITATIONS

 

 

 

 

MINIMUM SUPPLY AIR CFM

 

 

UNITMODEL SIZE NOMINAL

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

HEATER SIZE NOMINAL KW

 

 

TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

7

 

10

15

 

20

30

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

1100

1100

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

 

3

460-3-60

-

1100

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

1300

1300

 

1300

1300

 

1300

-

 

 

 

 

 

 

 

 

 

 

4

460-3-60

-

1300

 

1300

1300

 

1300

-

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

 

1300

1300

 

1400

-

 

 

 

 

 

 

 

 

 

 

 

208/230-3-60

1600

1600

 

1600

1600

 

1600

1600

 

 

 

 

 

 

 

 

 

 

5

460-3-60

1600

1600

 

1600

1600

 

1600

1600

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

1600

 

1600

1600

 

1600

1800

 

 

 

 

 

 

 

 

 

 

ECONOMIZER/MOTORIZED DAMPER AND RAIN HOOD

The instruction for the optional economizer/motorized damper and rain hood can be found in form 035- 07364-000. Use these instructions when field assem- bling an economizer rain hood onto a unit. The outdoor and return air dampers, the damper actuator, the damper linkage, the outdoor and return air divider baf- fles, and all the control sensors are factory mounted as part of the “Factory installed” economizer/motorized damper options.

POWER EXHAUST/BAROMETRIC RELIEF DAMPER AND RAIN HOOD

The instructions for the power exhaust/barometric relief damper and rain hood can be found in form 530.18- N1.10V.

All of the components, including the dampers, hard- ware, and mounting instructions are shipped in a single package external from the unit and must be field assembled and installed.

Power exhaust is only available as a field installed accessory.

ECONOMIZER AND POWER EXHAUST DAMPER SET POINT ADJUSTMENTS AND INFORMATION

Remove the economizer access panel from the unit. Loosen but do not remove the two panel latches. Locate the economizer control module, where the fol- lowing adjustments will be made.

Extreme care must be exercised in turning all setpoint, maximum, and minimum damper positioning adjustment screws to prevent twist- ing them off.

Check that the damper blades move smoothly without binding; carefully turn the Minimum Position Adjusting screw (found on the damper control module) fully clockwise and then set the thermostat indoor fan switch to the on position and then off, or energize and de- energize terminals “R” to “G”.