York 048 & 060 Unit Dimensions Rear View, Disconnect/Blower Access Location, Utilities Entry

Models: 048 & 060 BCH 036

1 36
Download 36 pages 12.15 Kb
Page 21
Image 21
FIGURE 10 - UNIT DIMENSIONS (REAR VIEW)

177820-YIM-A-0506

FIGURE 10 - UNIT DIMENSIONS (REAR VIEW)

FILTER

ACCESS

BLOWER MOTOR

ACCESS

DOT PLUGS

 

 

FIELD-SUPPLIED

 

 

DISCONNECT SWITCH

 

 

LOCATION

 

 

MOUNTING BRACKET

 

 

FOR DICONNECT SWITCH

 

 

(Shipped attached to the

 

 

blower housing inside

 

 

the blower compartment)

A,B

 

 

WIRING ENTRY

CONTROL BOX

 

(See Detail “B”)

ACCESS

DISCONNECT SWITCH LOCATION

AND MOTOR ACCESS PANEL FOR

UNIT WITH “BELT-DRIVE” OPTION

FIGURE 11 - DISCONNECT/BLOWER ACCESS LOCATION

TABLE 13: UTILITIES ENTRY

HOLE

OPENING SIZE (DIA.)

USED FOR

 

A

7/8” KO1

Control Wiring2

 

Side

 

Bottom

 

 

 

 

 

 

 

 

 

B

2” KO1

Power Wiring

 

Side

 

 

 

Bottom

 

 

 

 

 

 

 

 

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

 

 

 

 

 

1.Opening in the bottom to the unit can be located by the side in the insulation.

2.Do not remove the 2” knockout ring.

TABLE 14: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)

32” (Gas Heat)

 

 

 

Rear

12” (Less Economizer)

36” (With Economizer or Fixed

 

Air/Motorized Damper)

 

 

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

 

 

 

Right Side (Cond. Coil)

24”

Below Unit1

0”

Above Unit2

72” (For

Condenser Air Discharge)

 

1.Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2.Units must be installed outdoors. Overhanging struc- tures or shrubs should not obstruct condenser air dis- charge outlet.