TABLE 10: ELECTRICAL DATA - BCH036 - 060 BELT DRIVE (CONT.)
|
| COMPRESSORS | OD FAN | ID |
|
|
| MIN. | MAX. FUSE/ | |
MODEL | VOLTAGE | RLA | LRA | BLOWER | ELECTRIC HEATER | HEATER | HEATER | CIRCUIT | BRKR1 | |
MOTOR | MOTOR | MODEL NO. | KW | AMPS | AMPACITY | SIZE | ||||
|
| EACH | EACH | FLA | ||||||
|
| FLA |
|
|
| (AMPS) | (AMPS) | |||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| None | 31.6 | 40 | ||
|
|
|
|
|
| 2CE045105252 | 4.0 | 11.1 | 45.5 | 60 |
| 19.3 | 137.0 | 2.3 | 5.2 | 2CE045107252 | 5.6 | 15.5 | 51.1 | 60 | |
| 2CE04511025 | 8.0 | 22.2 | 59.4 | 70 | |||||
|
|
|
|
|
| 2CE04511525 | 11.9 | 33.0 | 72.9 | 80 |
|
|
|
|
|
| 2CE04512025 | 15.9 | 44.1 | 86.8 | 90 |
|
|
|
|
|
| 2CE04513025 | 22.2 | 61.6 | 108.7 | 110 |
|
|
|
|
|
| None | 31.6 | 40 | ||
|
|
|
|
|
| 2CE045105252 | 5.3 | 12.7 | 47.6 | 60 |
| 19.3 | 137.0 | 2.3 | 5.2 | 2CE045107252 | 7.5 | 18.0 | 54.2 | 60 | |
| 2CE04511025 | 10.6 | 25.5 | 63.5 | 70 | |||||
BCH060 |
|
|
|
|
| 2CE04511525 | 15.9 | 38.2 | 79.4 | 80 |
|
|
|
|
| 2CE04512025 | 21.2 | 51.0 | 95.4 | 100 | |
|
|
|
|
|
| 2CE04513025 | 29.6 | 71.2 | 120.6 | 125 |
|
|
|
|
|
| None | 16.4 | 25 | ||
|
|
|
|
|
| 2CE045107462 | 6.8 | 8.2 | 26.6 | 30 |
| 10.0 | 62.0 | 1.3 | 2.6 | 2CE045110462 | 10.1 | 12.1 | 31.6 | 35 | |
| 2CE045115462 | 13.6 | 16.4 | 36.8 | 40 | |||||
|
|
|
|
|
| |||||
|
|
|
|
|
| 2CE045120462 | 19.5 | 23.5 | 45.7 | 50 |
|
|
|
|
|
| 2CE045130462 | 28.8 | 34.6 | 59.7 | 60 |
|
|
|
|
|
| None | 12.9 | 20 | ||
| 7.9 | 50.0 | 1.3 | 2.0 | 2CE04511058 | 10.6 | 10.2 | 25.6 | 30 | |
| 2CE04511558 | 15.9 | 15.3 | 32.0 | 35 | |||||
|
|
|
|
|
| 2CE04512058 | 21.2 | 20.4 | 38.4 | 40 |
|
|
|
|
|
| 2CE04513058 | 30.4 | 29.3 | 49.4 | 50 |
1.HACR Type per NEC.
2.These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
18 | Unitary Products Group |