255027-YTG-B-0507

TABLE 7: BP036-072 HEATING CAPACITIES (CONT.)

Size

Air Over Evaporator

Capacity1

 

 

 

Outdoor Temperature (°F @ 72% RH)

 

 

Coil

 

& kW

 

 

 

 

(Tons)

 

 

 

 

 

 

 

 

 

CFM

 

DB (°F)

 

 

-10

0

10

20

30

40

50

60

 

 

 

 

 

 

 

55

MBH

 

11.3

20.8

30.3

39.8

49.2

58.7

68.2

77.7

 

 

 

KW

 

3.4

3.7

4.0

4.2

4.5

4.8

5.0

5.3

 

 

 

 

 

 

1800

 

70

MBH

 

10.1

19.6

29.0

38.5

48.0

57.5

66.9

76.4

 

 

KW

 

4.1

4.4

4.6

4.9

5.2

5.4

5.7

6.0

 

 

 

 

 

 

 

 

80

MBH

 

7.9

17.3

26.8

36.3

45.8

55.2

64.7

74.2

 

 

 

KW

 

4.6

4.8

5.1

5.4

5.6

5.9

6.2

6.4

 

 

 

 

 

 

 

 

55

MBH

 

13.2

22.6

32.1

41.6

51.1

60.5

70.0

79.5

072

 

 

KW

 

3.0

3.3

3.6

3.8

4.1

4.4

4.6

4.9

 

 

 

 

2400

 

70

MBH

 

11.9

21.4

30.9

40.4

49.8

59.3

68.8

78.3

(6)

 

KW

 

3.7

4.0

4.3

4.5

4.8

5.1

5.3

5.6

 

 

 

 

 

 

 

80

MBH

 

9.6

19.1

28.6

38.0

47.5

57.0

66.5

75.9

 

 

 

KW

 

4.2

4.4

4.7

5.0

5.2

5.5

5.8

6.0

 

 

 

 

 

 

 

 

55

MBH

 

13.8

23.2

32.7

42.2

51.7

61.1

70.6

80.1

 

 

 

KW

 

2.9

3.1

3.4

3.7

3.9

4.2

4.5

4.7

 

 

 

 

 

 

3000

 

70

MBH

 

12.5

22.0

31.5

40.9

50.4

59.9

69.4

78.8

 

 

KW

 

3.6

3.8

4.1

4.4

4.6

4.9

5.2

5.4

 

 

 

 

 

 

 

 

80

MBH

 

10.3

19.8

29.2

38.7

48.2

57.7

67.1

76.6

 

 

 

KW

 

4.0

4.3

4.5

4.8

5.1

5.3

5.6

5.9

 

 

 

 

 

1. These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh = 3.415 x kW.

TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (BP036 BELT DRIVE) - SIDE DUCT APPLICATION

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

 

 

 

 

AIR

 

 

 

 

 

 

 

 

FLOW

 

0.2

 

 

0.3

 

 

0.4

 

 

0.5

 

 

0.6

 

CFM

RPM

WATTS

BHP

RPM

WATTS

BHP

RPM

WATTS

BHP

RPM

WATTS

BHP

RPM

WATTS

BHP

800

-

-

-

-

-

-

696

357

0.38

743

389

0.42

786

422

0.45

900

-

-

-

656

353

0.38

706

385

0.41

753

417

0.45

797

450

0.48

1000

-

-

-

671

376

0.40

722

408

0.44

768

440

0.47

812

473

0.51

1100

634

364

0.39

690

398

0.43

741

431

0.46

787

463

0.50

831

496

0.53

1200

656

389

0.42

712

423

0.45

763

455

0.49

809

488

0.52

853

520

0.56

1300

681

418

0.45

737

452

0.49

787

485

0.52

834

517

0.55

877

550

0.59

1400

707

454

0.49

763

488

0.52

813

520

0.56

860

552

0.59

903

585

0.63

1500

735

496

0.53

791

530

0.57

841

562

0.60

887

594

0.64

931

627

0.67

1600

763

545

0.58

819

579

0.62

870

612

0.66

916

644

0.69

960

677

0.73

1700

793

602

0.65

849

636

0.68

900

669

0.72

946

701

0.75

990

734

0.79

1800

824

667

0.72

880

701

0.75

930

733

0.79

977

765

0.82

1021

798

0.86

1900

855

739

0.79

911

773

0.83

962

806

0.86

1008

838

0.90

1052

871

0.93

2000

887

819

0.88

943

853

0.92

994

886

0.95

1040

918

0.98

1084

951

1.02

AIR

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE - IWG1

 

 

 

 

FLOW

 

0.7

 

 

0.8

 

 

0.9

 

 

1.0

 

 

1.1

 

CFM

RPM

WATTS

BHP

RPM

WATTS

BHP

RPM

WATTS

BHP

RPM

WATTS

BHP

RPM

WATTS

BHP

800

829

457

0.49

872

495

0.53

916

538

0.58

964

586

0.63

1017

642

0.69

900

839

485

0.52

882

524

0.56

927

566

0.61

975

615

0.66

1027

670

0.72

1000

854

508

0.55

897

547

0.59

942

589

0.63

990

638

0.68

1043

693

0.74

1100

874

531

0.57

916

569

0.61

961

612

0.66

1009

660

0.71

1062

715

0.77

1200

896

555

0.60

938

594

0.64

983

636

0.68

1031

685

0.73

1084

740

0.79

1300

920

585

0.63

963

623

0.67

1007

666

0.71

1055

714

0.77

1108

770

0.83

1400

946

620

0.67

989

659

0.71

1034

701

0.75

1082

750

0.80

-

-

-

1500

974

662

0.71

1017

701

0.75

1061

743

0.80

1109

792

0.85

-

-

-

1600

1003

712

0.76

1045

750

0.80

1090

793

0.85

-

-

-

-

-

-

1700

1032

769

0.82

1075

807

0.87

-

-

-

-

-

-

-

-

-

1800

1063

833

0.89

1106

872

0.94

-

-

-

-

-

-

-

-

-

1900

1094

906

0.97

-

-

-

-

-

-

-

-

-

-

-

-

2000

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications. Factory Installed AK74 blower sheave and A39 belt.

AK61 blower sheave and A36 belt - Field installation required.

Unitary Products Group

15

Page 15
Image 15
York BP 036 warranty Available External Static Pressure IWG1 AIR Flow CFM RPM