255027-YTG-B-0507
TABLE 25: PHYSICAL DATA
| MODELS |
|
| BP |
| |
| 036 | 048 |
| 060 | 072 | |
|
|
| ||||
| Centrifugal Blower (Belt Drive) (Dia. x Wd. in.) | 12 x 10 | 12 x 10 |
| 12 x 10 | 12 x 11 |
EVAPORATOR | Centrifugal Blower (Direct Drive) (Dia. x Wd. in.) | 12 x 10 | 12 x 10 |
| 12 x 10 | 12 x 10 |
BLOWER |
|
|
|
|
|
|
Fan Motor HP (Direct Drive) | 3/4 | 1 |
| 1 | 1 | |
|
|
|
|
|
|
|
| Fan Motor HP (Belt Drive) | 1 1/2 | 1 1/2 |
| 1 1/2 | 1 1/2 |
|
|
|
|
|
|
|
EVAPORATOR | Rows Deep | 3 | 4 |
| 4 | 4 |
|
|
|
|
|
| |
Fins Per Inch | 13 | 13 |
| 13 | 13 | |
COIL |
| |||||
|
|
|
|
|
| |
Face Area (Sq. Ft.) | 5.1 | 5.1 |
| 5.1 | 5.1 | |
|
| |||||
|
|
|
|
|
|
|
CONDENSER | Propeller Dia. (in.) | 24 | 24 |
| 24 | 24 |
|
|
|
|
|
| |
Fan Motor Hp | 1/2 | 1/2 |
| 1/2 | 1/2 | |
FANS |
| |||||
|
|
|
|
|
| |
Nom. CFM | 4200 | 4200 |
| 4200 | 4200 | |
|
| |||||
|
|
|
|
|
|
|
CONDENSER | Rows Deep | 2 | 2 |
| 2 | 2 |
|
|
|
|
|
| |
Fins Per Inch | 18 | 18 |
| 18 | 18 | |
COILS |
| |||||
|
|
|
|
|
| |
Face Area (Sq. Ft.) | 17.1 | 17.1 |
| 17.1 | 17.1 | |
|
| |||||
|
|
|
|
|
|
|
COMPRESSOR | Quantity | 1 | 1 |
| 1 | 1 |
|
|
|
|
|
| |
Type | Reciprocal | Reciprocal |
| Scroll | Scroll | |
|
| |||||
|
|
|
|
|
|
|
AIR | Quantity Per Unit (15” X 20” X 1” or 2“) | 2 | 2 |
| 2 | 2 |
|
|
|
|
|
| |
Quantity Per Unit (14” X 25” X 1” or 2“) | 1 | 1 |
| 1 | 1 | |
FILTERS |
| |||||
|
|
|
|
|
| |
Total Face Area (sq. ft.) | 6.3 | 6.3 |
| 6.3 | 6.3 | |
|
| |||||
|
|
|
|
|
|
|
CHARGE | Refrigerant 22 (lbs./oz.) | 11/12 | 12/8 |
| 13/4 | 12/0 |
TABLE 26: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE | VOLTAGE | kW CAP. MULTI- | |
PLIER | |||
|
| ||
|
|
| |
208 | 208 | 0.75 | |
|
|
| |
240 | 230 | 0.92 | |
480 | 460 | 0.92 | |
600 | 575 | 0.92 |
TABLE 27: VOLTAGE LIMITATIONS1
POWER SUPPLY |
| VOLTAGE | |
|
|
| |
| MIN. |
| MAX. |
187 |
| 253 | |
|
|
|
|
187 |
| 253 | |
|
|
|
|
414 |
| 506 | |
518 |
| 506 |
1.Utilization Range “A” in accordance with ARI Standard 110.
Unitary Products Group | 33 |