TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (BP048 BELT DRIVE) - BOTTOM DUCT APPLICATION
AIR |
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
|
| |||||||
FLOW |
| 0.2 |
|
| 0.3 |
|
| 0.4 |
|
| 0.5 |
|
| 0.6 |
|
| 0.7 |
|
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | |
1000 | - | - | - | - | - | - | - | - | - | - | - | - | 833 | 564 | 0.61 | 879 | 605 | 0.65 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1100 | - | - | - | - | - | - | - | - | - | 809 | 549 | 0.59 | 854 | 592 | 0.63 | 900 | 633 | 0.68 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1200 | - | - | - | - | - | - | 786 | 538 | 0.58 | 830 | 581 | 0.62 | 875 | 623 | 0.67 | 920 | 664 | 0.71 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1300 | - | - | - | 766 | 535 | 0.57 | 808 | 574 | 0.62 | 851 | 617 | 0.66 | 896 | 659 | 0.71 | 942 | 700 | 0.75 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1400 | 749 | 541 | 0.58 | 789 | 576 | 0.62 | 830 | 616 | 0.66 | 874 | 658 | 0.71 | 918 | 701 | 0.75 | 964 | 742 | 0.80 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1500 | 774 | 587 | 0.63 | 813 | 622 | 0.67 | 855 | 662 | 0.71 | 898 | 705 | 0.76 | 943 | 747 | 0.80 | 989 | 788 | 0.85 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1600 | 801 | 639 | 0.69 | 840 | 674 | 0.72 | 881 | 714 | 0.77 | 925 | 757 | 0.81 | 970 | 799 | 0.86 | 1015 | 840 | 0.90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1700 | 830 | 697 | 0.75 | 869 | 732 | 0.79 | 911 | 772 | 0.83 | 954 | 814 | 0.87 | 999 | 857 | 0.92 | 1045 | 898 | 0.96 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1800 | 862 | 760 | 0.81 | 901 | 795 | 0.85 | 943 | 835 | 0.90 | 986 | 877 | 0.94 | 1031 | 920 | 0.99 | 1077 | 960 | 1.03 |
1900 | 897 | 828 | 0.89 | 936 | 863 | 0.93 | 977 | 903 | 0.97 | 1021 | 945 | 1.01 | 1066 | 988 | 1.06 | 1111 | 1029 | 1.10 |
2000 | 934 | 901 | 0.97 | 973 | 936 | 1.00 | 1015 | 976 | 1.05 | 1058 | 1018 | 1.09 | 1103 | 1061 | 1.14 | 1149 | 1102 | 1.18 |
2100 | 974 | 979 | 1.05 | 1013 | 1014 | 1.09 | 1055 | 1054 | 1.13 | 1098 | 1097 | 1.18 | 1143 | 1139 | 1.22 | 1189 | 1180 | 1.27 |
2200 | 1017 | 1063 | 1.14 | 1056 | 1098 | 1.18 | 1098 | 1138 | 1.22 | 1141 | 1180 | 1.27 | 1186 | 1223 | 1.31 | - | - | - |
2300 | 1063 | 1151 | 1.23 | 1102 | 1186 | 1.27 | 1144 | 1226 | 1.31 | 1187 | 1268 | 1.36 | - | - | - | - | - | - |
2400 | 1111 | 1243 | 1.33 | 1151 | 1278 | 1.37 | 1192 | 1318 | 1.41 | - | - | - | - | - | - | - | - | - |
2500 | 1163 | 1340 | 1.44 | 1202 | 1376 | 1.48 | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
| |||||||
AIR |
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
|
| |||||||
FLOW |
| 0.8 |
|
| 0.9 |
|
| 1.0 |
|
| 1.1 |
|
| 1.2 |
|
| 1.3 |
|
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | |
1000 | 925 | 642 | 0.69 | 971 | 673 | 0.72 | 1017 | 696 | 0.75 | 1061 | 708 | 0.76 | 1103 | 708 | 0.76 | 1144 | 693 | 0.74 |
1100 | 946 | 670 | 0.72 | 992 | 701 | 0.75 | 1037 | 723 | 0.78 | 1082 | 736 | 0.79 | 1124 | 735 | 0.79 | 1165 | 721 | 0.77 |
1200 | 967 | 701 | 0.75 | 1013 | 732 | 0.79 | 1058 | 755 | 0.81 | 1102 | 767 | 0.82 | 1145 | 767 | 0.82 | 1185 | 752 | 0.81 |
1300 | 988 | 737 | 0.79 | 1034 | 768 | 0.82 | 1079 | 791 | 0.85 | 1123 | 803 | 0.86 | 1166 | 803 | 0.86 | - | - | - |
1400 | 1010 | 779 | 0.84 | 1056 | 809 | 0.87 | 1102 | 832 | 0.89 | 1146 | 844 | 0.91 | 1188 | 844 | 0.91 | - | - | - |
1500 | 1035 | 825 | 0.89 | 1081 | 856 | 0.92 | 1126 | 879 | 0.94 | 1170 | 891 | 0.96 | - | - | - | - | - | - |
1600 | 1062 | 877 | 0.94 | 1108 | 908 | 0.97 | 1153 | 931 | 1.00 | 1197 | 943 | 1.01 | - | - | - | - | - | - |
1700 | 1091 | 935 | 1.00 | 1137 | 966 | 1.04 | 1182 | 988 | 1.06 | - | - | - | - | - | - | - | - | - |
1800 | 1123 | 997 | 1.07 | 1169 | 1028 | 1.10 | - | - | - | - | - | - | - | - | - | - | - | - |
1900 | 1157 | 1066 | 1.14 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
2000 | 1195 | 1139 | 1.22 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
2100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2200 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2300 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2400 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2500 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications. Factory Installed AK61 blower sheave and A36 belt.
AK56 blower sheave and A36 belt - Field installation required.
18 | Unitary Products Group |