TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (BP060 BELT DRIVE) - BOTTOM DUCT APPLICATION
AIR |
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
|
| |||||||
FLOW |
| 0.2 |
|
| 0.3 |
|
| 0.4 |
|
| 0.5 |
|
| 0.6 |
|
| 0.7 |
|
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | |
1000 | - | - | - | - | - | - | - | - | - | - | - | - | 862 | 453 | 0.49 | 901 | 498 | 0.53 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1100 | - | - | - | - | - | - | - | - | - | - | - | - | 883 | 494 | 0.53 | 922 | 539 | 0.58 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1200 | - | - | - | - | - | - | - | - | - | 866 | 489 | 0.53 | 904 | 536 | 0.58 | 943 | 581 | 0.62 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1300 | - | - | - | - | - | - | 850 | 488 | 0.52 | 889 | 535 | 0.57 | 928 | 581 | 0.62 | 967 | 627 | 0.67 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1400 | - | - | - | 836 | 491 | 0.53 | 875 | 537 | 0.58 | 913 | 584 | 0.63 | 952 | 631 | 0.68 | 991 | 676 | 0.73 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1500 | - | - | - | 862 | 545 | 0.58 | 901 | 591 | 0.63 | 940 | 638 | 0.68 | 978 | 685 | 0.73 | 1017 | 730 | 0.78 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1600 | 851 | 559 | 0.60 | 890 | 604 | 0.65 | 928 | 650 | 0.70 | 967 | 697 | 0.75 | 1006 | 744 | 0.80 | 1045 | 789 | 0.85 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1700 | 880 | 624 | 0.67 | 919 | 668 | 0.72 | 958 | 714 | 0.77 | 996 | 761 | 0.82 | 1035 | 808 | 0.87 | 1074 | 853 | 0.92 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1800 | 911 | 694 | 0.74 | 949 | 738 | 0.79 | 988 | 785 | 0.84 | 1027 | 832 | 0.89 | 1066 | 878 | 0.94 | 1105 | 923 | 0.99 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1900 | 942 | 770 | 0.83 | 981 | 814 | 0.87 | 1020 | 860 | 0.92 | 1059 | 907 | 0.97 | 1097 | 954 | 1.02 | 1136 | 999 | 1.07 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2000 | 976 | 851 | 0.91 | 1014 | 895 | 0.96 | 1053 | 941 | 1.01 | 1092 | 989 | 1.06 | 1130 | 1035 | 1.11 | 1169 | 1080 | 1.16 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2100 | 1010 | 938 | 1.01 | 1049 | 982 | 1.05 | 1087 | 1028 | 1.10 | 1126 | 1075 | 1.15 | 1165 | 1122 | 1.20 | 1204 | 1167 | 1.25 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2200 | 1046 | 1030 | 1.11 | 1084 | 1075 | 1.15 | 1123 | 1121 | 1.20 | 1162 | 1168 | 1.25 | 1200 | 1215 | 1.30 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2300 | 1082 | 1128 | 1.21 | 1121 | 1172 | 1.26 | 1160 | 1219 | 1.31 | 1198 | 1266 | 1.36 | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2400 | 1120 | 1231 | 1.32 | 1159 | 1276 | 1.37 | 1198 | 1322 | 1.42 | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2500 | 1159 | 1340 | 1.44 | 1198 | 1384 | 1.48 | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
AIR |
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
|
| |||||||
FLOW |
| 0.8 |
|
| 0.9 |
|
| 1.0 |
|
| 1.1 |
|
| 1.2 |
|
| 1.3 |
|
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | |
1000 | 940 | 541 | 0.58 | 980 | 579 | 0.62 | 1019 | 613 | 0.66 | 1059 | 641 | 0.69 | 1099 | 662 | 0.71 | 1140 | 674 | 0.72 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1100 | 961 | 582 | 0.62 | 1000 | 621 | 0.67 | 1040 | 654 | 0.70 | 1080 | 682 | 0.73 | 1120 | 703 | 0.75 | 1161 | 715 | 0.77 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1200 | 983 | 624 | 0.67 | 1022 | 663 | 0.71 | 1062 | 697 | 0.75 | 1101 | 725 | 0.78 | 1142 | 745 | 0.80 | 1182 | 758 | 0.81 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1300 | 1006 | 669 | 0.72 | 1045 | 708 | 0.76 | 1085 | 742 | 0.80 | 1125 | 770 | 0.83 | 1165 | 791 | 0.85 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1400 | 1030 | 718 | 0.77 | 1070 | 757 | 0.81 | 1109 | 791 | 0.85 | 1149 | 819 | 0.88 | 1190 | 840 | 0.90 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1500 | 1057 | 772 | 0.83 | 1096 | 811 | 0.87 | 1136 | 845 | 0.91 | 1176 | 873 | 0.94 | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1600 | 1084 | 831 | 0.89 | 1124 | 870 | 0.93 | 1163 | 904 | 0.97 | 1203 | 932 | 1.00 | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1700 | 1113 | 896 | 0.96 | 1153 | 935 | 1.00 | 1192 | 969 | 1.04 | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1800 | 1144 | 966 | 1.04 | 1183 | 1005 | 1.08 | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1900 | 1175 | 1042 | 1.12 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2000 | 1209 | 1123 | 1.20 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2200 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2300 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2400 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2500 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications. Factory Installed AK56 blower sheave and A36 belt.
20 | Unitary Products Group |