TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (BP072 BELT DRIVE) - BOTTOM DUCT APPLICATION
AIR |
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
|
|
| ||||||||
FLOW |
| 0.2 |
|
| 0.3 |
|
| 0.4 |
|
| 0.5 |
|
| 0.6 |
|
| 0.7 |
|
| 0.8 |
|
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | |
1500 | - | - | - | - | - | - | - | - | - | 923 | 639 | 0.69 | 956 | 702 | 0.75 | 990 | 766 | 0.82 | 1024 | 830 | 0.89 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1600 | - | - | - | - | - | - | 924 | 684 | 0.73 | 956 | 742 | 0.80 | 988 | 805 | 0.86 | 1022 | 870 | 0.93 | 1057 | 933 | 1.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1700 | - | - | - | 927 | 736 | 0.79 | 957 | 788 | 0.84 | 988 | 846 | 0.91 | 1021 | 909 | 0.97 | 1055 | 973 | 1.04 | 1089 | 1037 | 1.11 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1800 | 930 | 798 | 0.86 | 959 | 840 | 0.90 | 989 | 891 | 0.96 | 1021 | 950 | 1.02 | 1054 | 1013 | 1.09 | 1087 | 1077 | 1.16 | 1122 | 1141 | 1.22 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1900 | 963 | 902 | 0.97 | 992 | 944 | 1.01 | 1022 | 996 | 1.07 | 1053 | 1054 | 1.13 | 1086 | 1117 | 1.20 | 1120 | 1181 | 1.27 | 1155 | 1245 | 1.34 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2000 | 995 | 1007 | 1.08 | 1024 | 1049 | 1.13 | 1054 | 1101 | 1.18 | 1086 | 1159 | 1.24 | 1118 | 1222 | 1.31 | 1152 | 1287 | 1.38 | 1187 | 1350 | 1.45 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2100 | 1028 | 1113 | 1.19 | 1056 | 1155 | 1.24 | 1086 | 1207 | 1.29 | 1118 | 1265 | 1.36 | 1151 | 1328 | 1.42 | 1184 | 1393 | 1.49 | 1219 | 1456 | 1.56 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2200 | 1060 | 1221 | 1.31 | 1088 | 1262 | 1.35 | 1119 | 1314 | 1.41 | 1150 | 1372 | 1.47 | 1183 | 1435 | 1.54 | 1217 | 1500 | 1.61 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2300 | 1091 | 1329 | 1.43 | 1120 | 1371 | 1.47 | 1150 | 1422 | 1.53 | 1182 | 1481 | 1.59 | 1215 | 1544 | 1.66 | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2400 | 1123 | 1439 | 1.54 | 1152 | 1480 | 1.59 | 1182 | 1532 | 1.64 | 1214 | 1590 | 1.71 | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2500 | 1155 | 1549 | 1.66 | 1183 | 1591 | 1.71 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2600 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2700 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2800 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
AIR |
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
|
|
| ||||||||
FLOW |
| 0.9 |
|
| 1.0 |
|
| 1.1 |
|
| 1.2 |
|
| 1.3 |
|
| 1.4 |
|
| 1.5 |
|
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | |
1500 | 1060 | 890 | 0.95 | 1096 | 944 | 1.01 | 1133 | 989 | 1.06 | 1170 | 1022 | 1.10 | 1208 | 1042 | 1.12 | 1246 | 1044 | 1.12 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1600 | 1092 | 993 | 1.07 | 1129 | 1047 | 1.12 | 1165 | 1092 | 1.17 | 1203 | 1126 | 1.21 | 1240 | 1145 | 1.23 | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1700 | 1125 | 1097 | 1.18 | 1161 | 1151 | 1.23 | 1198 | 1196 | 1.28 | 1235 | 1229 | 1.32 | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1800 | 1158 | 1201 | 1.29 | 1194 | 1255 | 1.35 | 1231 | 1300 | 1.39 | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1900 | 1190 | 1305 | 1.40 | 1226 | 1359 | 1.46 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2000 | 1222 | 1410 | 1.51 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2100 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2200 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2300 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2400 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2500 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2600 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2700 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2800 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications. Factory Installed AK56 blower sheave and A36 belt.
22 | Unitary Products Group |