TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (BP072 BELT DRIVE) - SIDE DUCT APPLICATION
AIR |
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
|
|
| ||||||||
FLOW |
| 0.2 |
|
| 0.3 |
|
| 0.4 |
|
| 0.5 |
|
| 0.6 |
|
| 0.7 |
|
| 0.8 |
|
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | |
1500 | - | - | - | - | - | - | - | - | - | - | - | - | 935 | 658 | 0.71 | 967 | 721 | 0.77 | 1001 | 786 | 0.84 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1600 | - | - | - | - | - | - | - | - | - | 934 | 700 | 0.75 | 965 | 758 | 0.81 | 997 | 821 | 0.88 | 1031 | 886 | 0.95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1700 | - | - | - | - | - | - | 934 | 750 | 0.80 | 964 | 800 | 0.86 | 995 | 858 | 0.92 | 1028 | 921 | 0.99 | 1061 | 986 | 1.06 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1800 | - | - | - | 936 | 810 | 0.87 | 964 | 849 | 0.91 | 994 | 899 | 0.96 | 1025 | 958 | 1.03 | 1058 | 1020 | 1.09 | 1091 | 1085 | 1.16 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1900 | 939 | 885 | 0.95 | 966 | 910 | 0.98 | 994 | 949 | 1.02 | 1024 | 1000 | 1.07 | 1055 | 1058 | 1.13 | 1088 | 1121 | 1.20 | 1122 | 1185 | 1.27 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2000 | 969 | 986 | 1.06 | 996 | 1011 | 1.08 | 1024 | 1050 | 1.13 | 1054 | 1100 | 1.18 | 1085 | 1159 | 1.24 | 1118 | 1222 | 1.31 | 1152 | 1286 | 1.38 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2100 | 999 | 1088 | 1.17 | 1026 | 1113 | 1.19 | 1054 | 1152 | 1.24 | 1084 | 1202 | 1.29 | 1115 | 1261 | 1.35 | 1148 | 1324 | 1.42 | 1182 | 1388 | 1.49 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2200 | 1028 | 1191 | 1.28 | 1055 | 1216 | 1.30 | 1084 | 1255 | 1.35 | 1114 | 1306 | 1.40 | 1145 | 1364 | 1.46 | 1178 | 1427 | 1.53 | 1211 | 1491 | 1.60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2300 | 1058 | 1296 | 1.39 | 1085 | 1321 | 1.42 | 1114 | 1360 | 1.46 | 1143 | 1410 | 1.51 | 1175 | 1468 | 1.57 | 1207 | 1531 | 1.64 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2400 | 1087 | 1401 | 1.50 | 1114 | 1426 | 1.53 | 1143 | 1465 | 1.57 | 1173 | 1516 | 1.63 | 1204 | 1574 | 1.69 | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2500 | 1117 | 1509 | 1.62 | 1144 | 1533 | 1.65 | 1172 | 1573 | 1.69 | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2600 | 1146 | 1617 | 1.73 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2700 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2800 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
AIR |
|
|
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
|
|
| ||||||||
FLOW |
| 0.9 |
|
| 1.0 |
|
| 1.1 |
|
| 1.2 |
|
| 1.3 |
|
| 1.4 |
|
| 1.5 |
|
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | |
1500 | 1036 | 849 | 0.91 | 1072 | 908 | 0.97 | 1108 | 959 | 1.03 | 1146 | 999 | 1.07 | 1184 | 1026 | 1.10 | 1224 | 1035 | 1.11 | 1263 | 1024 | 1.10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1600 | 1066 | 949 | 1.02 | 1102 | 1008 | 1.08 | 1139 | 1059 | 1.14 | 1176 | 1099 | 1.18 | 1215 | 1126 | 1.21 | 1254 | 1135 | 1.22 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1700 | 1096 | 1049 | 1.13 | 1132 | 1107 | 1.19 | 1169 | 1159 | 1.24 | 1206 | 1199 | 1.29 | 1245 | 1225 | 1.31 | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1800 | 1126 | 1148 | 1.23 | 1162 | 1207 | 1.30 | 1199 | 1258 | 1.35 | 1237 | 1298 | 1.39 | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1900 | 1156 | 1249 | 1.34 | 1192 | 1307 | 1.40 | 1229 | 1358 | 1.46 | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2000 | 1186 | 1350 | 1.45 | 1222 | 1408 | 1.51 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2100 | 1216 | 1452 | 1.56 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2200 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2300 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2400 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2500 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2600 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2700 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2800 | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications. Factory Installed AK56 blower sheave and A36 belt.
Unitary Products Group | 21 |