York BP 036 warranty Unitary Products Group

Models: BP 036

1 44
Download 44 pages 48.53 Kb
Page 30
Image 30
Manual background

255027-YTG-B-0507

TABLE 23: ELECTRICAL DATA - BP036-072 DIRECT DRIVE W/POWERED CONVENIENCE OUTLET (CONT.)

 

 

COMPRESSORS

OD FAN

ID

CONV

 

 

 

MIN.

MAX. FUSE/

MODEL

VOLTAGE

 

 

BLOWER

ELECTRIC HEATER

HEATER

HEATER

CIRCUIT

BRKR1

TONNAGE

RLA

LRA

MOTOR

MOTOR

OUTLET

MODEL NO.

KW

AMPS

AMPACITY

SIZE

 

 

EACH

EACH

FLA

FLA

FLA

 

 

 

(AMPS)

(AMPS)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

54.2

70

 

 

 

 

 

 

 

2CE04510506

4.0

19.2

78.2

90

 

208-1-60

25.0

150.0

2.3

10.6

10.0

2CE04510706

5.6

26.9

87.8

100

 

2CE04511006

8.0

38.5

102.2

110

 

 

 

 

 

 

 

2CE04511506

11.9

57.2

125.7

150

 

 

 

 

 

 

 

2CE04512006

15.9

76.4

149.7

150

 

 

 

 

 

 

 

2CE04513006

22.2

106.7

187.6

200

 

 

 

 

 

 

 

None

--

--

54.2

70

 

 

 

 

 

 

 

2CE04510506

5.3

22.1

81.8

100

 

230-1-60

25.0

150.0

2.3

10.6

10.0

2CE04510706

7.5

31.3

93.2

110

 

2CE04511006

10.6

44.2

109.4

110

 

 

 

 

 

 

 

2CE04511506

15.9

66.3

137.0

150

060

 

 

 

 

 

 

2CE04512006

21.2

88.3

164.6

175

 

 

 

 

 

 

2CE04513006

29.6

123.3

208.3

225

(5)

 

 

 

 

 

 

None

--

--

44.5

60

 

 

 

 

 

 

 

2CE045105252

4.0

11.1

58.4

70

 

208-3-60

17.3

123.0

2.3

10.6

10.0

2CE045107252

5.6

15.5

64.0

70

 

2CE04511025

8.0

22.2

72.3

80

 

 

 

 

 

 

 

2CE04511525

11.9

33.0

85.8

90

 

 

 

 

 

 

 

2CE04512025

15.9

44.1

99.7

100

 

 

 

 

 

 

 

2CE04513025

22.2

61.6

121.6

125

 

 

 

 

 

 

 

None

--

--

44.5

60

 

 

 

 

 

 

 

2CE045105252

5.3

12.7

60.5

70

 

230-3-60

17.3

123.0

2.3

10.6

10.0

2CE045107252

7.5

18.0

67.1

70

 

2CE04511025

10.6

25.5

76.4

80

 

 

 

 

 

 

 

2CE04511525

15.9

38.2

92.3

100

 

 

 

 

 

 

 

2CE04512025

21.2

51.0

108.3

110

 

 

 

 

 

 

 

2CE04513025

29.6

71.2

133.5

150

 

 

 

 

 

 

 

None

--

--

46.9

60

 

 

 

 

 

 

 

2CE045105252

4.0

11.1

60.8

70

 

208-3-60

19.2

146.0

2.3

10.6

10.0

2CE045107252

5.6

15.5

66.3

80

 

2CE04511025

8.0

22.2

74.7

80

 

 

 

 

 

 

 

2CE04511525

11.9

33.0

88.2

90

072

 

 

 

 

 

 

2CE04512025

15.9

44.1

102.1

110

 

 

 

 

 

 

2CE04513025

22.2

61.6

123.9

125

(6)

 

 

 

 

 

 

None

--

--

46.9

60

 

 

 

 

 

 

 

2CE045105252

5.3

12.7

62.8

70

 

230-3-60

19.2

146.0

2.3

10.6

10.0

2CE045107252

7.5

18.0

69.5

80

 

2CE04511025

10.6

25.5

78.8

90

 

 

 

 

 

 

 

2CE04511525

15.9

38.2

94.7

100

 

 

 

 

 

 

 

2CE04512025

21.2

51.0

110.6

125

 

 

 

 

 

 

 

2CE04513025

29.6

71.2

135.9

150

1.HACR Type per NEC.

2.These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.

30

Unitary Products Group

Page 30
Image 30
York BP 036 warranty Unitary Products Group