York BP 036 warranty Belt Drive Blower Motor And Drive Data, Static Resistances

Models: BP 036

1 44
Download 44 pages 48.53 Kb
Page 24
Image 24

 

 

 

 

 

 

 

 

 

 

 

 

255027-YTG-B-0507

TABLE 18: BELT DRIVE BLOWER MOTOR AND DRIVE DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR BLOWER SPECIFICATION

 

 

 

 

 

 

MODEL

BLOWER

MOTOR1

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

 

BELT (NOTCHED)

 

RANGE

 

 

 

OUTSIDE

PITCH

BORE

 

OUTSIDE

PITCH

BORE

 

PITCH

 

SIZE

 

 

 

 

 

 

 

(RPM)

HP

FRAME

DESIGNATION

DIA.

DIA.

(IN.)

DESIGNATION

DIA.

DIA.

(IN.)

DESIGNATION

LENGTH

QTY.

 

 

 

 

 

(IN.)

(IN.)

 

 

(IN.)

(IN.)

 

 

(IN.)

 

036

600/920

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

5/8

AK74

7.2

7.0

1

A39

40.3

1

048

790/1120

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

5/8

AK61

5.9

5.7

1

A36

37.3

1

060

850/1220

1 1/2

56

1VL40

2.7-3.7

2.4-3.4

5/8

AK56

5.4

5.2

1

A36

37.3

1

072

900/1250

1 1/2

56

1VL44

3.1-4.1

2.8-3.8

7/8

AK56

5.4

5.2

1

A36

37.3

1

1.All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.

TABLE 19: STATIC RESISTANCES

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER1 3

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

ELECTRIC

7-15KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

HEATERS1

 

 

 

 

 

 

 

 

 

 

 

 

20-30KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

BOTTOM DUCT CONNECTIONS1

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

COOLING ONLY2

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

1.Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.

2.Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.

3.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 20: ELECTRIC HEATER CFM LIMITATIONS

UNIT MODEL SIZE

 

 

 

MINIMUM SUPPLY AIR CFM

 

 

VOLTAGE

 

 

HEATER SIZE NOMINAL KW

 

 

NOMINAL TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

7

 

10

15

 

20

30

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1100

1100

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

 

036

208/230-3-60

1100

1100

 

1200

1200

 

1300

-

(3)

460-3-60

-

1100

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1300

1300

 

1300

1300

 

1300

-

 

 

 

 

 

 

 

 

 

 

048

208/230-3-60

1300

1300

 

1300

1300

 

1300

-

(4)

460-3-60

-

1300

 

1300

1300

 

1300

-

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

 

1300

1300

 

1400

-

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1600

1600

 

1600

1600

 

1600

1600

 

 

 

 

 

 

 

 

 

 

060

208/230-3-60

1600

1600

 

1600

1600

 

1600

1600

(5)

460-3-60

1600

1600

 

1600

1600

 

1600

1600

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

1600

 

1600

1600

 

1600

1800

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1800

1800

 

1800

1800

 

1800

1800

 

 

 

 

 

 

 

 

 

 

072

208/230-3-60

1800

1800

 

1800

1800

 

1800

1800

(6)

460-3-60

-

1800

 

1800

1800

 

1800

1800

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

 

1800

1800

 

1800

1800

 

 

 

 

 

 

 

 

 

 

24

Unitary Products Group

Page 24
Image 24
York BP 036 warranty Belt Drive Blower Motor And Drive Data, Static Resistances, Electric Heater Cfm Limitations