255027-YTG-B-0507

TABLE 3:

BP036 COOLING CAPACITIES (3 TON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air on

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

75°F

 

 

 

 

 

 

 

85°F

 

 

 

 

 

77

42.7

2.1

16.5

13.3

10.3

-

-

-

41.2

2.4

16.1

13.1

10.0

-

-

-

750

72

39.8

2.1

22.0

19.0

16.1

13.1

-

-

37.9

2.4

21.5

18.5

15.5

12.5

-

-

67

36.8

2.1

27.5

24.8

21.8

18.9

15.9

-

34.7

2.4

27.0

24.0

20.9

17.9

14.9

-

 

 

62

35.2

2.1

35.1

28.3

25.7

22.7

19.8

16.8

33.4

2.3

33.3

28.1

24.7

21.7

18.6

15.6

 

77

44.9

2.1

18.5

15.1

11.6

-

-

-

42.9

2.4

18.3

14.8

11.3

-

-

-

 

72

41.7

2.1

24.9

21.5

18.1

14.7

-

-

39.5

2.4

24.4

20.9

17.4

13.9

-

-

900

67

38.6

2.1

31.4

28.0

24.6

21.2

17.8

-

36.2

2.4

30.5

27.0

23.5

20.0

16.5

-

 

62

36.9

2.1

36.9

32.3

28.9

25.5

22.1

18.7

34.8

2.3

34.8

31.3

27.8

24.3

20.8

17.3

 

57

34.3

2.1

34.3

33.3

29.8

26.4

23.0

19.6

33.1

2.3

33.1

31.8

28.3

24.8

21.3

17.8

 

77

47.0

2.1

20.4

16.8

12.9

-

-

-

44.7

2.4

20.4

16.5

12.5

-

-

-

 

72

43.7

2.1

27.9

24.0

20.1

16.3

-

-

41.1

2.4

27.3

23.3

19.3

15.4

-

-

1050

67

40.5

2.1

35.3

31.2

27.3

23.5

19.6

-

37.6

2.4

34.1

30.1

26.1

22.2

18.2

-

 

62

38.7

2.1

38.6

36.4

32.2

28.3

24.4

20.6

36.2

2.3

36.2

34.4

30.8

26.9

22.9

18.9

 

57

36.0

2.1

36.0

35.4

33.2

29.3

25.5

21.6

34.4

2.4

34.4

33.8

31.4

27.5

23.5

19.6

 

77

49.1

2.1

22.3

18.6

14.2

-

-

-

46.4

2.4

22.6

18.2

13.8

-

-

-

 

72

45.7

2.1

30.8

26.5

22.2

17.8

-

-

42.8

2.4

30.1

25.7

21.2

16.8

-

-

1200

67

42.3

2.2

39.3

34.4

30.1

25.8

21.4

-

39.1

2.4

37.6

33.2

28.7

24.3

19.9

-

 

62

40.4

2.1

40.4

40.4

35.4

31.1

26.8

22.4

37.6

2.4

37.6

37.6

33.9

29.5

25.0

20.6

 

57

37.6

2.1

37.6

37.6

36.5

32.2

27.9

23.6

35.8

2.4

35.8

35.8

34.6

30.1

25.7

21.3

 

72

46.4

2.1

32.8

28.0

23.1

18.3

-

-

43.4

2.4

32.1

27.2

22.3

17.4

-

-

1350

67

42.9

2.1

41.4

36.2

31.4

26.6

21.8

-

39.7

2.4

39.0

35.0

30.1

25.2

20.3

-

62

41.0

2.1

41.0

41.0

37.0

32.2

27.3

22.5

38.2

2.4

38.2

38.2

35.5

30.6

25.7

20.8

 

 

57

38.2

2.1

38.2

38.2

37.6

32.8

28.0

23.2

36.4

2.4

36.4

36.4

35.7

30.8

25.9

21.0

 

72

47.1

2.1

34.8

29.5

24.1

18.8

-

-

44.1

2.4

34.1

28.7

23.3

17.9

-

-

1500

67

43.6

2.1

43.6

38.1

32.8

27.4

22.1

-

40.3

2.4

40.3

36.9

31.5

26.1

20.7

-

62

41.7

2.1

41.7

41.7

38.6

33.2

27.9

22.6

38.8

2.4

38.8

38.8

37.1

31.8

26.4

21.0

 

 

57

38.8

2.1

38.8

38.8

38.8

33.4

28.1

22.8

36.9

2.4

36.9

36.9

36.9

31.5

26.1

20.7

 

 

 

 

 

95°F

 

 

 

 

 

 

 

105°F

 

 

 

 

 

77

39.6

2.6

15.6

12.8

9.7

-

-

-

36.1

2.9

13.5

11.7

8.5

-

-

-

750

72

36.1

2.6

21.1

18.0

14.9

11.8

-

-

33.0

2.8

20.1

16.9

13.7

10.5

-

-

67

32.6

2.6

26.5

23.1

20.0

17.0

13.9

-

29.9

2.8

26.7

22.1

18.9

15.7

12.5

-

 

 

62

31.6

2.5

31.6

27.8

23.7

20.6

17.5

14.4

29.1

2.8

29.1

26.2

21.7

18.5

15.2

12.0

 

77

41.0

2.7

18.1

14.5

10.9

-

-

-

37.3

2.9

17.0

13.2

9.5

-

-

-

 

72

37.3

2.6

23.9

20.3

16.7

13.1

-

-

34.1

2.9

22.9

19.2

15.4

11.7

-

-

900

67

33.7

2.6

29.7

26.1

22.5

18.9

15.3

-

30.9

2.8

28.8

25.1

21.4

17.6

13.9

-

 

62

32.7

2.6

32.7

30.2

26.6

23.0

19.4

15.8

30.1

2.8

30.1

28.1

24.4

20.7

17.0

13.3

 

57

31.9

2.6

31.9

30.4

26.8

23.2

19.6

16.0

28.9

2.8

28.9

28.2

24.6

20.9

17.2

13.5

 

77

42.3

2.7

20.5

16.1

12.1

-

-

-

38.5

2.9

20.4

14.8

10.6

-

-

-

 

72

38.6

2.6

26.6

22.6

18.5

14.5

-

-

35.2

2.9

25.6

21.4

17.2

13.0

-

-

1050

67

34.8

2.6

32.8

29.0

25.0

20.9

16.8

-

31.9

2.8

30.9

28.0

23.8

19.6

15.3

-

 

62

33.7

2.6

33.7

32.5

29.5

25.4

21.4

17.3

31.1

2.8

31.1

30.1

27.2

23.0

18.8

14.6

 

57

32.9

2.6

32.9

32.2

29.7

25.6

21.6

17.5

29.9

2.8

29.9

29.5

27.4

23.2

18.9

14.7

 

77

43.7

2.7

22.9

17.8

13.3

-

-

-

39.8

2.9

23.8

16.4

11.7

-

-

-

 

72

39.8

2.6

29.4

24.9

20.3

15.8

-

-

36.3

2.9

28.4

23.6

18.9

14.2

-

-

1200

67

35.9

2.6

35.9

32.0

27.4

22.9

18.3

-

32.9

2.9

32.9

30.9

26.2

21.5

16.8

-

 

62

34.8

2.6

34.8

34.8

32.4

27.8

23.3

18.7

32.1

2.8

32.1

32.1

30.0

25.3

20.5

15.8

 

57

34.0

2.6

34.0

34.0

32.6

28.1

23.5

19.0

30.9

2.8

30.9

30.9

30.2

25.4

20.7

16.0

 

72

40.4

2.7

31.4

26.4

21.4

16.4

-

-

36.8

2.9

30.2

25.1

19.9

14.8

-

-

1350

67

36.5

2.6

36.5

33.8

28.8

23.8

18.8

-

33.3

2.9

33.3

32.0

27.5

22.4

17.2

-

62

35.4

2.6

35.4

35.4

34.0

29.1

24.1

19.1

32.5

2.8

32.5

32.5

31.4

26.2

21.1

15.9

 

 

57

34.5

2.6

34.5

34.5

33.8

28.8

23.9

18.9

31.2

2.8

31.2

31.2

30.9

25.7

20.5

15.4

 

72

41.1

2.7

33.3

27.9

22.4

17.0

-

-

37.2

2.9

32.1

26.5

20.9

15.3

-

-

1500

67

37.0

2.6

37.0

35.7

30.2

24.8

19.3

-

33.7

2.9

33.7

33.0

28.9

23.3

17.7

-

62

35.9

2.6

35.9

35.9

35.7

30.3

24.8

19.4

32.9

2.8

32.9

32.9

32.8

27.2

21.6

16.0

 

 

57

35.1

2.6

35.1

35.1

35.1

29.6

24.2

18.7

31.6

2.8

31.6

31.6

31.6

26.0

20.4

14.8

8

Unitary Products Group

Page 8
Image 8
York BP 036 warranty BP036 Cooling Capacities 3 TON, 75F 85F