York DJ 060, DJ 048, DJ 036 Physical Data, Electric Heat Correction Factors, VOLTAGE LIMITATIONS1

Models: DJ 060 DJ 036 DJ 048

1 48
Download 48 pages 53.8 Kb
Page 35
Image 35

036-21687-002-A-1105

TABLE 30: PHYSICAL DATA

 

MODELS

 

DJ

 

 

036

048

060

 

 

EVAPORATOR

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

12 X 10

12 X 10

BLOWER

Fan Motor HP (Belt Drive)

1-1/2

1-1/2

1-1/2

 

 

 

 

 

EVAPORATOR

Rows Deep

3

4

4

 

 

 

 

Fins Per Inch

13

13

13

COIL

 

 

 

 

Face Area (Sq. Ft.)

5.1

5.1

5.1

 

 

 

 

 

 

CONDENSER

Propeller Dia. (in.)

24

24

24

 

 

 

 

Fan Motor Hp

1/2

1/2

1/2

FANS

 

 

 

 

Nom. CFM

4200

4200

4200

 

 

 

 

 

 

CONDENSER

Rows Deep

2

2

2

 

 

 

 

Fins Per Inch

18

18

18

COILS

 

 

 

 

Face Area (Sq. Ft.)

17.1

17.1

17.1

 

 

 

 

 

 

COMPRESSOR

Quantity

1

1

1

(Qty. Per Unit)

Type

Recip.

Recip.

Scroll

 

 

 

 

 

AIR

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

2

 

 

 

 

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

1

FILTERS

 

 

 

 

Total Face Area (sq. ft.)

6.3

6.3

6.3

 

 

 

 

 

 

CHARGE

Refrigerant 22 (lbs./oz.)

9/4

9/8

11/0

TABLE 31: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTI-

PLIER

 

 

208

208

1.00

 

 

 

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 32: VOLTAGE LIMITATIONS1

POWER SUPPLY

 

VOLTAGE

 

 

 

 

MIN.

 

MAX.

208/230-1-60

187

 

252

 

 

 

 

208/230-3-60

187

 

252

 

 

 

 

460-3-60

432

 

504

575-3-60

540

 

630

1.Utilization Range “A” in accordance with ARI Standard 110.