York DJ 036, DJ 048, DJ 060 warranty Vertical Ducted Inlet, Vertical Ducted Discharge

Models: DJ 060 DJ 036 DJ 048

1 48
Download 48 pages 53.8 Kb
Page 16
Image 16

036-21687-002-A-1105

TABLE 6: DJ036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET)

UNIT DESCRIPTION / MODEL

 

 

DJ036 / 3 Ton / Belt Drive

 

 

CONFIGURATION

 

 

 

Vertical Ducted Inlet

 

 

 

Indoor Blower Speed (RPM)

632

632

881

883

Blower Static Pressure (IWG)

0.2

0.3

0.2

0.7

Airflow (CFM)

1069

870

1903

917

Blower Motor BHP

0.36

0.33

0.71

0.49

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

Octave Center Freq.

Operation2

Operation2

Operation2

Operation2

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

78

82

78

82

80

85

80

84

125

70

75

70

74

71

80

71

79

250

55

60

55

60

59

61

58

62

500

47

50

47

50

52

53

49

52

1000

40

43

39

43

50

51

45

46

2000

37

40

37

39

45

46

41

43

4000

36

37

36

37

45

46

40

40

8000

44

44

44

44

45

47

44

44

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 7: DJ036 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

 

 

DJ036 / 3 Ton / Belt Drive

 

 

CONFIGURATION

 

 

Vertical Ducted Discharge

 

 

Indoor Blower Speed (RPM)

632

632

881

883

Blower Static Pressure (IWG)

0.2

0.3

0.2

0.7

Airflow (CFM)

1069

870

1903

917

Blower Motor BHP

0.36

0.33

0.71

0.49

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

Octave Center Freq.

Operation2

Operation2

Operation2

Operation2

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

80

83

80

83

83

86

82

85

125

78

79

77

78

80

83

79

82

250

55

60

54

59

63

63

58

62

500

48

51

46

50

58

59

52

53

1000

41

44

39

43

54

55

48

49

2000

37

40

35

38

50

50

42

44

4000

38

39

36

37

52

53

44

44

8000

44

45

44

44

49

50

45

45

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

16

Unitary Products Group

Page 16
Image 16
York DJ 036, DJ 048, DJ 060 warranty Vertical Ducted Inlet, Vertical Ducted Discharge