York DJ 048 Unit Dimensions Rear View, Disconnect/Blower Access Location, Utilities Entry, Hole

Models: DJ 060 DJ 036 DJ 048

1 48
Download 48 pages 53.8 Kb
Page 39
Image 39
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)

036-21687-002-A-1105

FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)

FILTER

ACCESS

BLOWER MOTOR

ACCESS

DOT PLUGS

 

 

FIELD-SUPPLIED

 

 

DISCONNECT SWITCH

 

 

LOCATION

 

 

MOUNTING BRACKET

 

 

FOR DICONNECT SWITCH

 

 

(Shipped attached to the

 

 

blower housing inside

 

 

the blower compartment)

A,B

 

 

WIRING ENTRY

CONTROL BOX

 

(See Detail “B”)

ACCESS

DISCONNECT SWITCH LOCATION

AND MOTOR ACCESS PANEL FOR

UNIT WITH “BELT-DRIVE” OPTION

FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION

TABLE 33: UTILITIES ENTRY

HOLE

OPENING SIZE (DIA.)

USED FOR

A

7/8” KO1

Control Wiring2

Side

Bottom

 

 

 

 

 

 

 

B

2” KO1

Power Wiring

Side

 

Bottom

 

 

 

 

 

 

 

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

 

 

 

 

1.Opening in the bottom to the unit can be located by the side in the insulation.

2.Do not remove the 2” knockout ring.

TABLE 34: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)

32” (Gas Heat)

 

 

 

Rear

12” (Less Economizer)

36” (With Economizer or Fixed

 

Air/Motorized Damper)

 

 

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

 

 

 

Right Side (Cond. Coil)

24”

Below Unit1

0”

Above Unit2

72” (For

Condenser Air Discharge)

 

 

 

1.Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2.Units must be installed outdoors. Overhanging struc- tures or shrubs should not obstruct condenser air dis- charge outlet.

Unitary Products Group

39

Page 39
Image 39
York DJ 048 Unit Dimensions Rear View, Disconnect/Blower Access Location, Utilities Entry, Minimum Clearances, Hole