TABLE 28: ELECTRICAL DATA - DJ036, 048 & 060 BELT DRIVE W/O POWERED CONVENIENCE OUTLET (CONT)
|
| COMPRESSORS | OD FAN | ID | CONV |
|
|
| MIN. | MAX. FUSE/ | |
MODEL | VOLTAGE |
|
| BLOWER | ELECTRIC HEATER | HEATER | HEATER | CIRCUIT | BRKR1 | ||
|
| ||||||||||
TONNAGE | RLA | LRA | MOTOR | MOTOR | OUTLET | MODEL NO. | KW | AMPS | AMPACITY | SIZE | |
|
| EACH | EACH | FLA | FLA | FLA |
|
|
| (AMPS) | (AMPS) |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| None | 41.2 | 45 | ||
|
|
|
|
|
|
| 2CE04510506 | 4.0 | 19.2 | 41.2 | 45 |
| 25.0 | 150.0 | 2.3 | 7.6 | 0.0 | 2CE04510706 | 5.6 | 26.9 | 43.2 | 60 | |
| 2CE04511006 | 8.0 | 38.5 | 57.6 | 60 | ||||||
|
|
|
|
|
|
| 2CE04511506 | 11.9 | 57.2 | 81.0 | 90 |
|
|
|
|
|
|
| 2CE04512006 | 15.9 | 76.4 | 105.1 | 110 |
|
|
|
|
|
|
| 2CE04513006 | 22.2 | 106.7 | 142.9 | 150 |
|
|
|
|
|
|
| None | 41.2 | 45 | ||
|
|
|
|
|
|
| 2CE04510506 | 5.3 | 22.1 | 41.2 | 45 |
| 25.0 | 150.0 | 2.3 | 7.6 | 0.0 | 2CE04510706 | 7.5 | 31.3 | 48.6 | 60 | |
| 2CE04511006 | 10.6 | 44.2 | 64.7 | 70 | ||||||
|
|
|
|
|
|
| 2CE04511506 | 15.9 | 66.3 | 92.3 | 100 |
|
|
|
|
|
|
| 2CE04512006 | 21.2 | 88.3 | 119.9 | 125 |
|
|
|
|
|
|
| 2CE04513006 | 29.6 | 123.3 | 163.7 | 175 |
|
|
|
|
|
|
| None | 29.1 | 35 | ||
|
|
|
|
|
|
| 2CE045105252 | 4.0 | 11.1 | 29.1 | 35 |
| 17.3 | 123.0 | 2.3 | 5.2 | 0.0 | 2CE045107252 | 5.6 | 15.5 | 29.1 | 35 | |
| 2CE04511025 | 8.0 | 22.2 | 34.3 | 45 | ||||||
DJ060 |
|
|
|
|
|
| 2CE04511525 | 11.9 | 33.0 | 47.8 | 50 |
|
|
|
|
|
| 2CE04512025 | 15.9 | 44.1 | 61.7 | 70 | |
|
|
|
|
|
|
| 2CE04513025 | 22.2 | 61.6 | 83.5 | 90 |
|
|
|
|
|
|
| None | 29.1 | 35 | ||
|
|
|
|
|
|
| 2CE045105252 | 5.3 | 12.7 | 29.1 | 35 |
| 17.3 | 123.0 | 2.3 | 5.2 | 0.0 | 2CE045107252 | 7.5 | 18.0 | 29.1 | 35 | |
| 2CE04511025 | 10.6 | 25.5 | 38.4 | 45 | ||||||
|
|
|
|
|
|
| 2CE04511525 | 15.9 | 38.2 | 54.3 | 60 |
|
|
|
|
|
|
| 2CE04512025 | 21.2 | 51.0 | 70.2 | 80 |
|
|
|
|
|
|
| 2CE04513025 | 29.6 | 71.2 | 95.5 | 100 |
|
|
|
|
|
|
| None | 14.4 | 20 | ||
|
|
|
|
|
|
| 2CE045107462 | 6.8 | 8.2 | 14.4 | 20 |
| 8.4 | 70.0 | 1.3 | 2.6 | 0.0 | 2CE045110462 | 10.1 | 12.1 | 18.4 | 20 | |
| 2CE045115462 | 13.6 | 16.4 | 23.7 | 25 | ||||||
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| 2CE045120462 | 19.5 | 23.5 | 32.6 | 35 |
|
|
|
|
|
|
| 2CE045130462 | 28.8 | 34.6 | 46.6 | 50 |
|
|
|
|
|
|
| None | 11.8 | 15 | ||
| 7.0 | 53.0 | 1.3 | 2.0 | 0.0 | 2CE04511058 | 10.6 | 10.2 | 15.2 | 20 | |
| 2CE04511558 | 15.9 | 15.3 | 21.6 | 25 | ||||||
|
|
|
|
|
|
| 2CE04512058 | 21.2 | 20.4 | 28.0 | 30 |
|
|
|
|
|
|
| 2CE04513058 | 30.4 | 29.3 | 39.1 | 40 |
1.HACR Type per NEC.
2.These electric heaters do not include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB0470086 are available for field installation.
32 | Unitary Products Group |