York DJ 048 Belt Drive Blower Motor And Drive Data, Static Resistances, 036-21687-002-A-1105

Models: DJ 060 DJ 036 DJ 048

1 48
Download 48 pages 53.8 Kb
Page 30
Image 30

036-21687-002-A-1105

TABLE 25: BELT DRIVE BLOWER MOTOR AND DRIVE DATA

 

 

MOTOR1

ADJUSTABLE MOTOR PULLEY

 

FIXED BLOWER PULLEY

 

 

BELT

 

MODEL

BLOWER

 

 

(NOTCHED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

RANGE

 

 

DESIG-

OUTSIDE

PITCH

 

BORE

DESIG-

OUTSIDE

PITCH

 

BORE

DESIG-

PITCH

 

(RPM)

 

 

 

 

 

 

HP

FRAME

NATION

DIA.

DIA.

 

(IN.)

NATION

DIA.

DIA.

 

(IN.)

NATION

LENGTH

QTY.

 

 

 

 

 

 

 

 

 

(IN.)

(IN.)

 

 

 

(IN.)

(IN.)

 

 

 

(IN.)

 

DJ036

600/920

1-1/2

56

1VL40

2.7-3.7

2.4-3.4

 

5/8

AK74

7.2

7.0

 

1

A39

40.3

1

DJ048

790/1120

1-1/2

56

1VL40

2.7-3.7

2.4-3.4

 

5/8

AK61

5.9

5.7

 

1

A36

37.3

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DJ060

850/1220

1-1/2

56

1VL40

2.7-3.7

2.4-3.4

 

5/8

AK56

5.4

5.2

 

1

A36

37.3

1

1.All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.

TABLE 26: STATIC RESISTANCES

 

 

 

 

 

 

RESISTANCE, IWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER1,3

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

ELECTRIC

7-15KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

HEATERS1

 

 

 

 

 

 

 

 

 

 

 

 

20-30KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING ONLY2

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

1.Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.

2.Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.

3.The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

TABLE 27: ELECTRIC HEATER CFM LIMITATIONS

 

 

 

 

MINIMUM SUPPLY AIR CFM

 

 

UNIT MODEL SIZE

 

 

 

 

 

 

 

 

 

VOLTAGE

 

 

HEATER SIZE NOMINAL KW

 

 

NOMINAL TONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

7

 

10

15

 

20

30

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1100

1100

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

 

3

208/230-3-60

1100

1100

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

460-3-60

-

1100

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

 

1200

1200

 

1300

-

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1300

1300

 

1300

1300

 

1300

-

 

 

 

 

 

 

 

 

 

 

4

208/230-3-60

1300

1300

 

1300

1300

 

1300

-

 

 

 

 

 

 

 

 

 

460-3-60

-

1300

 

1300

1300

 

1300

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

-

 

1300

1300

 

1400

-

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

1600

1600

 

1600

1600

 

1600

1600

 

 

 

 

 

 

 

 

 

 

5

208/230-3-60

1600

1600

 

1600

1600

 

1600

1600

 

 

 

 

 

 

 

 

 

460-3-60

1600

1600

 

1600

1600

 

1600

1600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-3-60

-

1600

 

1600

1600

 

1600

1800

 

 

 

 

 

 

 

 

 

 

30

Unitary Products Group

Page 30
Image 30
York DJ 048, DJ 036, DJ 060 Belt Drive Blower Motor And Drive Data, Static Resistances, Electric Heater Cfm Limitations