TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (DJ036 BELT DRIVE) - SIDE DUCT APPLICATION
AIR |
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
| |||||||
FLOW |
| 0.2 |
|
| 0.3 |
|
| 0.4 |
|
| 0.5 |
|
| 0.6 |
| |
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | ||
| ||||||||||||||||
800 | 696 | 357 | 0.38 | 743 | 389 | 0.42 | 786 | 422 | 0.45 | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
900 | 656 | 353 | 0.38 | 706 | 385 | 0.41 | 753 | 417 | 0.45 | 797 | 450 | 0.48 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
1000 | 671 | 376 | 0.40 | 722 | 408 | 0.44 | 768 | 440 | 0.47 | 812 | 473 | 0.51 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
1100 | 634 | 364 | 0.39 | 690 | 398 | 0.43 | 741 | 431 | 0.46 | 787 | 463 | 0.50 | 831 | 496 | 0.53 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
1200 | 656 | 389 | 0.42 | 712 | 423 | 0.45 | 763 | 455 | 0.49 | 809 | 488 | 0.52 | 853 | 520 | 0.56 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
1300 | 681 | 418 | 0.45 | 737 | 452 | 0.49 | 787 | 485 | 0.52 | 834 | 517 | 0.55 | 877 | 550 | 0.59 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
1400 | 707 | 454 | 0.49 | 763 | 488 | 0.52 | 813 | 520 | 0.56 | 860 | 552 | 0.59 | 903 | 585 | 0.63 | |
1500 | 735 | 496 | 0.53 | 791 | 530 | 0.57 | 841 | 562 | 0.60 | 887 | 594 | 0.64 | 931 | 627 | 0.67 | |
1600 | 763 | 545 | 0.58 | 819 | 579 | 0.62 | 870 | 612 | 0.66 | 916 | 644 | 0.69 | 960 | 677 | 0.73 | |
1700 | 793 | 602 | 0.65 | 849 | 636 | 0.68 | 900 | 669 | 0.72 | 946 | 701 | 0.75 | 990 | 734 | 0.79 | |
1800 | 824 | 667 | 0.72 | 880 | 701 | 0.75 | 930 | 733 | 0.79 | 977 | 765 | 0.82 | 1021 | 798 | 0.86 | |
1900 | 855 | 739 | 0.79 | 911 | 773 | 0.83 | 962 | 806 | 0.86 | 1008 | 838 | 0.90 | 1052 | 871 | 0.93 | |
2000 | 887 | 819 | 0.88 | 943 | 853 | 0.92 | 994 | 886 | 0.95 | 1040 | 918 | 0.98 | 1084 | 951 | 1.02 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
AIR |
|
|
|
| AVAILABLE EXTERNAL STATIC PRESSURE - IWG1 |
|
|
|
| |||||||
FLOW |
| 0.7 |
|
| 0.8 |
|
| 0.9 |
|
| 1.0 |
|
| 1.1 |
| |
CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | RPM | WATTS | BHP | ||
| ||||||||||||||||
800 | 829 | 457 | 0.49 | 872 | 495 | 0.53 | 916 | 538 | 0.58 | 964 | 586 | 0.63 | 1017 | 642 | 0.69 | |
900 | 839 | 485 | 0.52 | 882 | 524 | 0.56 | 927 | 566 | 0.61 | 975 | 615 | 0.66 | 1027 | 670 | 0.72 | |
1000 | 854 | 508 | 0.55 | 897 | 547 | 0.59 | 942 | 589 | 0.63 | 990 | 638 | 0.68 | 1043 | 693 | 0.74 | |
1100 | 874 | 531 | 0.57 | 916 | 569 | 0.61 | 961 | 612 | 0.66 | 1009 | 660 | 0.71 | 1062 | 715 | 0.77 | |
1200 | 896 | 555 | 0.60 | 938 | 594 | 0.64 | 983 | 636 | 0.68 | 1031 | 685 | 0.73 | 1084 | 740 | 0.79 | |
1300 | 920 | 585 | 0.63 | 963 | 623 | 0.67 | 1007 | 666 | 0.71 | 1055 | 714 | 0.77 | 1108 | 770 | 0.83 | |
1400 | 946 | 620 | 0.67 | 989 | 659 | 0.71 | 1034 | 701 | 0.75 | 1082 | 750 | 0.80 | ||||
1500 | 974 | 662 | 0.71 | 1017 | 701 | 0.75 | 1061 | 743 | 0.80 | 1109 | 792 | 0.85 | ||||
1600 | 1003 | 712 | 0.76 | 1045 | 750 | 0.80 | 1090 | 793 | 0.85 | |||||||
1700 | 1032 | 769 | 0.82 | 1075 | 807 | 0.87 | ||||||||||
1800 | 1063 | 833 | 0.89 | 1106 | 872 | 0.94 | ||||||||||
1900 | 1094 | 906 | 0.97 | |||||||||||||
2000 | ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1. Blower performance includes gas heat exchangers and 1” filters. See STATIC RESISTANCE table for additional applications. Factory Installed AK74 blower sheave and A39 belt.
AK61 blower sheave and A36 belt - Field installation required.
24 | Unitary Products Group |