York DJ 048 036-21687-002-A-1105, Other Pre-Engineeredaccessories Available, •Electric Heaters

Models: DJ 060 DJ 036 DJ 048

1 48
Download 48 pages 53.8 Kb
Page 45
Image 45

036-21687-002-A-1105

OPTIONAL OUTDOOR AIR (Shall be made available by

either/or):

ELECTRONIC ENTHALPY AUTOMATIC ECONO- MIZER- Outdoor and return air dampers that are inter- locked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti- ometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi- tioned space during normal operation. During econo- mizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer oper- ation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The out- door intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/fil- ters shall be provided. Simultaneous economizer/com- pressor operation is also possible. Dampers shall fully close on power loss.

MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position,spring-return damper actuator. The maximum leakage rate for the out- door air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pres- sure differential of 0.5 IWG. A unit-mounted potentiome- ter shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB - 14"and 8” high, full perimeter curb with wood nailer (shipped knocked-down).

BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit.

PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.

HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude.

HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit.

LOW NOX - Required to reduce the emission of nitrogen oxides below 40 nanograms per joule.

GAS PIPING - Contains 1/2” pipe nipples, fittings and gas cock (including panel assess gaskets) required for bottom gas supply connection with external shut off.

POWER EXHAUST OPTION - To work in conjunction with economizers.

ELECTRIC HEATERS

ECONOMIZER/MOTORIZED DAMPER RAIN HOOD - Contains all hood panels and the hardware for assem- bling.

MANUAL OUTDOOR AIR DAMPER

COIL GUARD KIT - Guard for cooling coil.

HAIL GUARD

FLUE EXHAUST EXTENSION

OTHER FACTORY INSTALLED OPTIONS

POWER EXHAUST OPTION - To work in conjunction with economizers.

STAINLESS STEEL HEAT EXCHANGER

STAINLESS STEEL DRAIN PAN

BOTTOM DRAIN CONNECTION

TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL

ELECTRONIC SINGLE ENTHALPY ECONOMIZER

DIRTY FILTER SWITCH

PHASE MONITOR

COIL GUARD

POWERED GFI CONVENIENCE OUTLET

NON-POWERED GFI CONVENIENCE OUTLET

BAS CONTROLS (Simplicity™ INTELLI-Comfort™,

CPC, JOHNSON, HONEYWELL, NOVAR)

BAS READY ECONOMIZER (BELIMO ACTUATOR WITHOUT A CONTROLLER)

HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS

2" PLEATED FILTERS

DISCONNECT SWITCH

SUPPLY AIR SMOKE DETECTOR

RETURN AIR SMOKE DETECTOR

Unitary Products Group

45

Page 45
Image 45
York DJ 048 036-21687-002-A-1105, Other Pre-Engineeredaccessories Available, •Electric Heaters, Manual Outdoor Air Damper