TABLE 4: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

UNIT DESCRIPTION / MODEL

 

 

DJ036 / 3 Ton / Belt Drive

 

 

CONFIGURATION

 

 

 

Horizontal Ducted Inlet

 

 

 

Indoor Blower Speed (RPM)

630

631

879

885

Blower Static Pressure (IWG)

0.2

0.3

0.2

0.7

Airflow (CFM)

1116

928

1979

1020

Blower Motor BHP

0.41

0.37

0.76

0.53

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

 

Cooling

ID Blower

Cooling

Octave Center Freq.

Operation2

Operation2

 

Operation2

Operation2

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

 

(dB)

Only (dB)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

80

82

80

82

78

 

83

81

85

125

76

77

76

77

82

 

83

81

82

250

56

59

56

60

60

 

61

58

60

500

50

50

49

50

54

 

54

51

52

1000

40

43

39

42

49

 

50

44

45

2000

41

42

40

42

49

 

49

43

44

4000

41

41

41

41

49

 

49

41

41

8000

45

45

45

45

47

 

47

45

45

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 5: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

 

 

DJ036 / 3 Ton / Belt Drive

 

 

CONFIGURATION

 

 

Horizontal Ducted Discharge

 

 

Indoor Blower Speed (RPM)

630

631

879

885

Blower Static Pressure (IWG)

0.2

0.3

0.2

0.7

Airflow (CFM)

1116

928

1979

1020

Blower Motor BHP

0.41

0.37

0.76

0.53

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

Octave Center Freq.

Operation2

Operation2

Operation2

Operation2

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

63

80

84

80

83

85

87

84

87

125

74

77

74

76

80

82

80

83

250

58

61

58

61

68

68

63

65

500

48

51

47

50

58

58

53

54

1000

41

45

39

43

55

55

49

50

2000

39

41

37

39

53

53

46

47

4000

41

41

38

38

55

55

49

49

8000

45

45

44

44

52

53

47

47

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.