York DJ 048 COOLING ONLY 24 VOLT THERMOSTAT, Typical Control Wiring, Unit Terminal, STRIP TB1

Models: DJ 060 DJ 036 DJ 048

1 48
Download 48 pages 53.8 Kb
Page 36
Image 36
REFER TO THE ELECTRICAL DATA

036-21687-002-A-1105

TYPICAL POWER WIRING

 

 

REFER TO THE ELECTRICAL DATA

 

 

 

 

 

 

TABLES TO SIZE THE DISCONNECT

 

 

 

 

 

 

SWITCH, OVERCURRENT PROTEC-

 

 

 

 

 

 

TION AND WIRING.

 

 

 

 

 

 

TYPICAL CONTROL WIRING

 

 

COOLING ONLY (24 VOLT THERMOSTAT)

COOLING / HEATING (24 VOLT THERMOSTAT)

 

 

 

 

 

 

 

THERMOSTAT1

 

 

THERMOSTAT1

UNIT TERMINAL

 

TERMINALS

 

 

TERMINALS

STRIP TB1

 

 

RH

UNIT TERMINAL

 

 

 

 

 

STRIP TB1

 

 

 

 

ADD

 

 

RV

R

 

 

 

 

 

JUMPER

RC

R

 

 

 

 

 

YC

Y1

24 VOLT

 

Y

Y1

 

TRANSFORMER

 

24 VOLT

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

Y2

 

 

 

Y2

 

 

 

 

 

 

 

 

 

 

 

W

W1

 

GF

G

 

 

 

 

 

 

 

 

 

 

W2

 

C

124 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.

GG

C

124 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT, USE THERMOSTAT 2TH0471024.

COOLING / HEATING (ELECTRONIC THERMOSTAT)

COOLING / HEATING (ELECTRONIC THERMOSTAT)

 

 

 

MULTI STAGE

 

 

 

SINGLE STAGE

 

 

 

 

 

 

 

 

 

 

THERMOSTAT1

 

 

 

 

 

 

 

TERMINALS

 

UNIT TERMINAL

 

 

THERMOSTAT1

 

ADD

 

RC

 

 

STRIP TB1

24 VOLT

 

 

 

RH

 

 

R

TRANSFORMER

 

TERMINALSUNIT TERMINAL

JUMPER

 

 

 

 

 

 

Y1

 

 

Y1

 

 

 

STRIP TB1

 

 

 

 

 

 

 

 

 

 

Y2

 

2

Y2

 

 

RH

 

 

 

 

 

 

 

 

 

4

W1

 

 

W1

 

 

RC

R

 

W2

 

3

W2

 

ADD

 

 

 

 

 

 

 

Y

Y1

 

 

G

 

 

G

 

JUMPER

 

 

 

 

 

 

 

 

 

B

 

 

C

 

W

W1

 

 

 

 

 

 

 

 

LED 1

 

 

X

 

 

G

G

 

 

LED 2

NOT

 

OCC

 

 

 

 

 

 

 

 

 

 

 

COM

USED

4

 

 

 

 

C

ADD

 

A1

 

 

 

 

 

 

24 VOLT

JUMPER

 

A2

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

T

 

TO REMOTE SENSOR

 

 

 

TTION AND WIRING. 2TH040702224 IF USED

1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).

2SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.

3SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRIC HEATER OR 2 STAGE GAS HEAT.

4REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE THERMOSTAT SWITCHES TO THE SET-BACK POSITION.

1ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).

TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT 2TH04700224.

FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING

36

Unitary Products Group

Page 36
Image 36
York DJ 048, DJ 036 COOLING ONLY 24 VOLT THERMOSTAT, Typical Control Wiring, Unit Terminal, STRIP TB1, Volt, Transformer