York HFC-410A manual Model

Models: HFC-410A

1 44
Download 44 pages 7.36 Kb
Page 15
Image 15
MODEL

FORM 100.50-EG5 (108)

TABLE 3 – PHYSICAL DATA (cont’d)

MODEL

050

051

060

061

Filters - 12" rigid 65%, 2" 30% prefilter (pre-filter position)

 

 

 

 

Quantity

1 / 4 / 9

1 / 4 / 9

1 / 4 / 9

1 / 4 / 9

Size (length x width) (in.)

16x20/25x16/25x20

16x20/25x16/25x20

16x20/25x16/25x20

16x20/25x16/25x20

Total Filter Face Area (square feet)

43.0

43.0

43.0

43.0

Filters - 12" rigid 95%, 2" 30% prefilter (pre-filter position)

 

 

 

 

Quantity

1 / 4 / 9

1 / 4 / 9

1 / 4 / 9

1 / 4 / 9

Size (length x width) (in.)

16x20/25x16/25x20

16x20/25x16/25x20

16x20/25x16/25x20

16x20/25x16/25x20

Total Filter Face Area (square feet)

44.6

44.6

44.6

44.6

Filters - 2" carbon (pre-filter position - angled)

 

 

 

 

Quantity

8 / 12

8 / 12

8 / 12

8 / 12

16x20/25x16/25x20

25x16/25x20

25x16/25x20

25x16/25x20

25x16/25x20

Total Filter Face Area (square feet)

63.9

63.9

63.9

63.9

Filters - 12" rigid rack only, with 2" throwaways

 

 

 

 

Quantity

1 / 4 / 9

1 / 4 / 9

1 / 4 / 9

1 / 4 / 9

Size (length x width) (in.)

16x20/25x16/25x20

16x20/25x16/25x20

16x20/25x16/25x20

16x20/25x16/25x20

Total Filter Face Area (square feet)

43

43

43

43

MODEL

050

051

060

061

Gas Furnaces

 

 

 

375 MBH / 300 MBH / 1 steps

 

Staged Furnace Sizes (input/output/steps)

 

 

750 MBH / 600 MBH / 2 steps

 

 

 

 

1125 MBH / 900 MBH / 3 steps

 

Gas Pressure Range

 

4.5" - 13.5"

4.5" - 13.5"

4.5" - 13.5"

4.5" - 13.5"

 

 

IWC

IWC

IWC

IWC

Minimum OA Temp for Mech. Cig.

 

40°F

40°F

40°F

40°F

Low Ambient Option Min. OA Temp

 

0

0

0

0

Minimum Airflow (Heating)

375

7,500

7,500

11,500

11,500

750

14,000

14,000

14,000

14,000

 

Bottom Supply Only

1,125

21,000

21,000

21,000

21,000

JOHNSON CONTROLS

15