HEATING OPERATION

FORM 100.50-EG5 (108)

is called from the thermostat, the Supply Fan will start. Ventilation functions (if equipped) will be permitted to run with an occupied signal. Economizer functions will operate with a “G” call and a call for cooling.

HEATING OPERATION

Thermostat Control

If a 7-wire thermostat (2 Cool/2 Heat) controls the unit, all zone-temperature setpoint-control is maintained at

the thermostat. With this operation, the unit remains idle until it receives a stage call from the thermostat. If “G” is called from the thermostat, the Supply Fan will start. Ventilation functions (if equipped) will be permitted to run with an occupied signal.

TABLE 22 – POWER-SUPPLY-CONDUCTOR SIZE RANGE

 

 

 

Dual-Point TB

 

 

 

 

 

Supply

Single-Point

Single-Point

TB 1

TB 2

Voltage

TB

Disconnect

 

 

208V

(2*) 250 kcmil-500 kcmil

(2*) 2 AWG-500 kcmil

6 AWG-400 kcmil

6 AWG-350 kcmil

 

 

 

 

 

230V

(2*) 250 kcmil-500 kcmil

(2*) 2 AWG-500 kcmil

6 AWG-400 kcmil

6 AWG-350 kcmil

 

 

 

 

 

460V

6 AWG-400 kcmil

6 AWG-350 kcmil

14 AWG-2/0

14 AWG-2/0

 

 

 

 

 

575V

6 AWG-400 kcmil

6 AWG-350 kcmil

14 AWG-2/0

14 AWG-2/0

 

 

 

 

 

NOTE: 2* = Dual pairs per phase