System Manager/Zone Coordinator User’s Manual 65
428516-YUM-B-0908
6. Press the button for the zone parameter you want to change. The button label
describes the current setting. When you press the button, the appropriate screen
appears allowing you to change the value. Table17 lists these parameters and
their ranges or possible selections.
7. If you want to edit the name of the zone, press the Edit Zone Name button. On
the Zone Name screen that appears, use the on-screen keyboard to enter a new
name. Click OK to save.
8. If you want to apply these zone settings to all zones currently defined, press the
Copy Zone Setup to All Other Zones button. A confirmation message appears.
Press OK to perform the copy operation.
9. After you complete the zone setup changes, press OK. The Zone Setup screen
returns, reflecting the changes you made.
Table 17: VAV RTU Zone Setup Parameters
Parameter Parameter Range/Selections
Thermostat Warm/Cool Adjust Enabled or Disabled
Temporary Occupancy Input Enabled or Disabled
Supply Area Valid range 0.001 to 9.999 sq ft
Supply Pickup Gain Valid range 0.001 to 9.999
Heating Unocc Min Flow Valid range 0 to 9,999 cfm
Heating Occ Min Flow Valid range 0 to 9,999 cfm
Cooling Occ Min Flow Valid range 0 to 9,999 cfm
Cooling Unocc Min Flow Valid range 0 to 9,999 cfm
Heating Unocc Setpoint Valid range 55.0 to 68.0 Deg F1
1. Heating Unoccupied <= Heating Occupied <= Cooling Occupied <= Cooling Unoccupied
Heating Occ Setpoint Valid range 62.0 to 72.0 Deg F1
Cooling Occ Setpoint Valid range 68.0 to 78.0 Deg F1
Cooling Unocc Setpoint Valid range 75.0 to 90.0 Deg F1
Cooling Max Flow Valid range 53 to 9,999 cfm
Warm-up Min Flow Valid range 0 to 9,999 cfm
CO2 Ventilation Cutoff Valid range 0 to 2,000 ppm
Box Mode Auto, Open, Closed, Minimum Position, Maximum
Position