System Manager/Zone Coordinator User’s Manual 79
428516-YUM-B-0908
6. Enable the point by pressing the Not Used button. Click OK, then edit the
point’s definition. If you want to change the Open and Closed text for a binary
point, use the on-screen keyboard to enter a name, then click OK to save. Also
consider the following:
The Instant Shutdown point is dedicated to BI1 on the IOM Controller at
address 4. When you enable this point and push the button connected to
BI1, all zoning systems for the site shutdown.
The Alarm Horn point is dedicated to BO1 on the IOM Controller at
address 4. When you enable this point, any device connected to BO1 is
energized whenever the System Manager/Coordinator detects a new alarm.
The Alarm Horn engages and disengages in concert with the Alarm LED
on the System Manager/Coordinator.
7. If you want to provide a name for the point, press the Edit Point Name button.
On the Point Name screen that appears, use the on-screen keyboard to enter a
name. Click OK to save.
8. After you complete the Auxiliary Points setup changes, press the Back button.
The Auxiliary Points Selection screen returns, reflecting the changes you
made.
AI2 Temperature, Humidity, or CO2
BI2 Up to 24 characters (default: On and Off)
BO2 Up to 24 characters (default: On and Off)
BO3 Up to 24 characters (default: On and Off)
BO4 Up to 24 characters (default: On and Off)
1. The Instant Shutdown switch is reserved for BI1 on IOM address 4.
2. The Alarm Horn output is reserved for BO1 on IOM at address 4.
Table 20: IOM Points Setup Selections (Part 2 of 2)
Parameter Parameter Range/Selections