System Manager/Zone Coordinator User’s Manual62
428516-YUM-B-0908
6. Press the button for the zone parameter you want to change. The button label
describes the current setting. When you press the button, the appropriate screen
appears, allowing you to change the value. Table15 lists these parameters and
their ranges or possible selections.
a. If you want to edit the name of the zone, press the Edit Zone Name button.
On the Zone Name screen that appears, use the on-screen keyboard to enter
a new name. Click OK to save.
b. If you want to apply these zone settings to all zones currently defined, press
the Copy Zone Setup to All Other Zones button. A confirmation message
appears. Press OK to perform the copy operation.
7. After you complete the zone setup changes, press OK. The Zone Setup screen
returns, reflecting the changes you made.
Setting Up a CV RTU Zone
To set up a CV RTU zone:
1. From the Home screen, press the Setup icon. The System Manager Setup
screen appears.
2. Press the Systems button, then select the CV RTU that contains the zone you
want to configure. The CV RTU Setup and Status screen appears.
Table 15: Zone Setup Parameters
Parameter Parameter Range/Selections
Votin g Enabled or Disabled
Heating Unocc Setpoint Valid range 55.0 to 70.0 Deg F1
1. Heating Unoccupied <= Heating Occupied <= Cooling Occupied <= Cooling Unoccupied
Thermostat Warm / Cool Adjust Enabled or Disabled
Heating Occ Setpoint Valid range 62.0 to 75.0 Deg F1
Temporary Occupancy Input Enabled or Disabled
Cooling Occ Setpoint Valid range 68.0 to 88.0 Deg F1
Cooling Unocc Setpoint Valid range 75.0 to 90.0 Deg F1
Max Damper Position Valid range 0 to 100%2
2. Minimum position <= Maximum Position
Heating Min Damper Position Valid range 0 to 100%2
Cooling Min Damper Position Valid range 0 to 100%2