Emerson Series 610 manual Maintenance

Page 104

Maintenance

4.0MAINTENANCE

4.1Safety Precautions

Observe the safety precautions in Important Safety Instructions on page 1 and in 1.3 - Safety Precautions.

ONLY qualified service personnel should perform maintenance on the UPS system.

Observe ALL of the WARNINGS below before performing ANY maintenance on the UPS System and associated equipment. Also observe the manufacturer’s safety precautions pertaining to the battery, along with the battery safety precautions in this section.

! CAUTION

Always identify connecting wiring prior to disconnecting any wiring. Do not substitute parts except as authorized by Liebert Corporation.

Maintain the UPS cabinets free of foreign materials such as solder, wire cuttings, etc.

Contact Liebert Global Services if you are not sure of the procedures to follow or if you are not familiar with the circuitry.

! WARNING

Extreme caution is required when performing maintenance.

Be constantly aware that the UPS system contains high DC as well as AC voltages. With input power off and the battery disconnected, high voltage at filter capacitors and power circuits should be discharged within 30 seconds. However, if a power circuit failure has occurred, you should assume that high voltage may still exist after shutdown. Check with a voltmeter before making contact.

AC voltage will remain on the bypass and output circuit breakers and the static bypass switch, unless associated external circuit breakers are opened.

Check for voltage with both AC and DC voltmeters prior to making contact.

Be sure to read the battery manufacturer’s manual before working on or near the battery. Battery terminals will constantly be energized, regardless of whether the UPS is operating or not.

When the UPS system is under power, both the operator and any test equipment must be isolated from direct contact with earth ground and the UPS chassis frame by using rubber mats.

Some components within the cabinets are not connected to chassis ground.

Any contact between floating circuits and the chassis is a lethal shock hazard. Use differential oscilloscopes when measuring a floating circuit. The differential input should have at least 800 vrms common mode input rating and a common mode rejection ratio of at least 80dB.

Exercise caution that the test instrument exterior does not make contact, either physically or electrically, with earth ground.

In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or others approved for use in fighting electrical fires.

98

Image 104
Contents Liebert Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Multi-Module UPS, 100-500kVAMulti-Module UPS, 500-750kVA Designed for Success ReliabilityTypes of System Control Cabinets SCCs Safety Precautions Input Power FailureModes of Operation Other Factors to ConsiderOperator Controls 1989-2003 Battery OptionsBattery Racks or Cabinets Module Battery DisconnectThree Breaker Maintenance Bypass Two Breaker Maintenance BypassGeneral Component Descriptions System Control CabinetBattery Plant UPS ModuleSoftware Detailed Component DescriptionsControls Hardware Input Power Factor Rectifier/ChargerOperation Input Circuit BreakerBattery Charging Circuit Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitNon-Linear Load Characteristics Unbalanced Load CharacteristicsInverter Output Regulation and Overload PerformanceShorted SCR Monitoring Static BypassFuse Protection Load Transfers Static Switch IsolationPulsed Parallel Operation Transfer and Retransfer Conditions Redundant Mode Retransfer InhibitedFeatures Display Screen and Operator ControlsDescription Function 500kVA1000kVA Operation Description Location Function Refer to 3.4.5 Shutdown ProceduresNumbers are used as keys to data in , below Switches behind SCC control panel door Menu Tree Navigation Menu treeModule Master Menu Master Menu ScreenSCC Master Menu Operation Output Metering Displays SCC Monitor/Mimic Display ScreenInput Metering Displays Status/Alarm Message Areas Item 7 Alarm MessagesItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Module Monitor/Mimic display screenAlarm Messages Item 5 Alarm MessagesSCC Display Module DisplayMonitor/Mimic display example Utility fail 2700kVAKVA//2170 KWkW 325A0A 325A0A 325A0A Upsinputpwr Battery MOD 1 OFF Line SUM ALM MVODLTS2 OFF540 Line SUM ALM Walk-In Display Screen Walk-in display screen during start-upStatus Reports Screens Present StatusModule Status Report Event HistorySCC Status Report History Status History status report screensAlarm conditions that freeze history data gathering Alarm in SCC Alarm in ModuleBattery Cycle Monitor-Module Only System StatusBattery cycle monitoring summary screen System Configuration Screens SCC system configuration screenDate Date screenTime Time screenAuto dial setting screen Auto DialModem Baud Rate Maximum Auto-Retransfer AttemptsSystem Current Rating Language SelectionSystem Options Retransfer AttemptsBattery test screen-MMU only Continuous Duty Static Switch OptionalRemote Monitor SCC and module remote monitor indicationsAlarm Limit Settings Screen Module alarm limit settings screenBattery Float Voltage Temperature Limit Setting OptionalLoad Transfer Procedures Screen Refer to 3.4.3 Load Transfer Procedures for more detailsStart-Up Procedures Screen Refer to 3.4.1 SCC Start-Up Procedure for more detailsShutdown Procedures Screen Module start- up procedures screensSCC shutdown procedures screen Battery Time Screen Module Only Battery time screen 15 minute dischargeUpper Limit Actual Lower Limit Elapsed Time MinutesOperation Meter Calibration Screen Meter calibration screenBattery Equalize Screen Battery equalize screenAlarm and Status Messages Module Status Messages System Status MessagesAbbreviation Definition Abbreviations used in alarm messagesLoad Block Messages Alarm messages meaning and corrective action Manual Reset Static SwitchBypass Phase Control PowerReverse Power Inverter FaultTransfer Module N OffBattery Overtemp OvertemperatureTimeout New AlarmSpecial Functions Alarm messages summaryAlarm Message Communication Interfaces Worldwide ReportingAuto-Dial Requesting InformationSite Reporting SiteScan or Snmp Local Reporting to a TerminalLocal Reporting to a Monitor Separate / Simultaneous Outputs Liebert Series 610 terminal commandsRemote Monitor Panel Circuit breaker abbreviations Abbreviation Circuit Breaker Load on Bypass OK to TransferLoad on bypass, UPS available Momentary overload, pulsed static bypass switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOne Module Off-Line One module off-line, load on UPSOff Battery Load on UPS-battery not availableRefer to 3.4.5 Shutdown Procedures Emergency Modules OffRemote Emergency Power Off Emergency power offRefer to 3.3.10 Maintenance Bypass System ShutdownLoad on maintenance bypass, two breakers Refer to 3.5 Automatic Operations for more details Manual ProceduresSCC Start-Up Procedure Operation Operation SCC start-up procedures screen UPS Module Start-Up Module start-up procedures screen Operation Load Transfer Procedures Manual Transfer Instructions UPS LeadIf the load is on the UPS System Bypass Maintenance Bypass Load TransfersIf the load is on Maintenance Bypass Shutdown Procedures System Shutdown Procedure Module Shutdown Procedure Local Emergency Modules Off Lemo Remote Emergency Power Off RepoAutomatic Operations Overloads Without Transfer Automatic Transfers to Bypass1000% 150%Automatic Emergency Modules Off Automatic Retransfers to UPSAutomatic Module Off-Line Maintenance Liebert Global Services Maintenance Agreements The Signature ProgramProfessional Start-Up TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatRack-Mounted Batteries Battery retorque valuesBattery voltage record Torque Requirements Torque specifications unless otherwise labeledDetection of Trouble Reporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Recommended Test EquipmentKVA Power factor pf KVARating Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Specifications 112 Page Locations
Related manuals
Manual 112 pages 3.63 Kb

Series 610 specifications

The Emerson Series 610 is a cutting-edge solution for precise process measurement and control, designed specifically for industries where accuracy and reliability are paramount. This advanced instrument, often utilized in oil and gas, chemical processing, and water treatment sectors, combines innovative technology with robust features to meet the demanding requirements of modern industrial applications.

One of the standout features of the Series 610 is its exceptional measurement accuracy. The device employs advanced sensor technology that enables precise determination of variables such as pressure, temperature, and flow. This accuracy translates into improved process efficiency and enhanced product quality. With a wide range of measurement capabilities, the Series 610 can handle varying process conditions and fluid types, making it versatile across different applications.

The heart of the Emerson Series 610 lies in its intelligent diagnostics and predictive maintenance functionalities. This built-in technology allows for real-time monitoring of the device's operational status, providing valuable insights into performance trends. By detecting anomalies early, users can take proactive measures to prevent potential failures, thereby reducing downtime and maintenance costs.

Moreover, the Series 610 is designed with user-friendly features. Its intuitive interface and easy-to-navigate menus facilitate quick setup and configuration, enabling operators to be productive from the outset. The device also supports various communication protocols, including HART and FOUNDATION fieldbus, ensuring seamless integration into existing control systems and enhancing overall automation capabilities.

Another notable characteristic of the Emerson Series 610 is its robust construction. Designed to withstand harsh environmental conditions, it is built with durable materials that offer high resistance to corrosion and physical damage. This durability ensures longevity and reliability, even in the most challenging industrial environments.

In summary, the Emerson Series 610 represents a significant advancement in process measurement technology. With its exceptional accuracy, intelligent diagnostics, user-friendly design, and robust construction, it is an ideal choice for industries seeking to enhance their operational efficiency and reliability. Its ability to seamlessly integrate into existing systems further solidifies its position as a leading solution in the field of industrial measurement and control. As industries continue to evolve, the Series 610 is poised to meet the challenges of the future with confidence and precision.