Emerson Series 610 manual Environmental Conditions, Specifications applicable to environment

Page 115

Specifications

5.2Environmental Conditions

Table 17 Specifications applicable to environment

Enclosure

The UPS is housed in a NEMA-1 enclosure. The enclosure is designed for indoor use only

and is not to be subjected to falling objects or precipitation.

 

 

 

 

 

 

 

Recommended Operating

25°C ambient

 

 

Temperature

 

 

 

 

 

Maximum Operating

40°C ambient (design temperature) without derating (see Notes 1- 3).

Temperature

 

 

 

Minimum Operating

0°C

 

 

Temperature

 

 

 

 

 

Storage Temperature

-20°C to 70°C

 

 

 

 

Typical Battery

Average annual temperature shall not exceed 27°C. Peak temperature shall not exceed

Temperature Requirements

43°C during any 24-hour period. See battery manufacturer’s recommendations.

Relative Humidity

0 to 95% without condensation

 

 

 

 

Operating Elevation

Sea level to 1219 meters (4000 ft.) without derating

 

 

 

 

Storage Elevation

Sea level to 15,000 meters (50,000 ft.)

 

 

 

 

Audible Noise, measured

62-69 dBA typical for 100-450kVA units

 

72 dBA typical for 500-750kVA units

 

5 feet from unit

 

75 dBA typical for 1000kVA units

 

 

 

 

 

 

 

 

98% at 45°C

 

 

 

 

 

 

Derating for Higher

96% at 50°C

 

 

 

 

 

93% at 55°C

 

 

Ambient Temperatures

 

 

(see Note 3)

Consult your Liebert sales representative regarding applications in high ambient

 

temperatures or call 1-800-LIEBERT. Special temperature sensors must be installed at the

 

factory.

 

 

 

 

% Derating @ 104°F (40°C)

% Derating @ 95°F (35°C)

 

Elevation-ft. (m)

Ambient (see Note 3)

Ambient (see Note 3)

 

5000 (1524)

98%

100%

 

 

 

 

 

5249 (1600)

98%

100%

 

 

 

 

Derating for Higher

5906 (1800)

97%

99%

 

 

 

6562 (2000)

96%

98%

Elevations

(see Note 4)

7218 (2200)

95%

97%

 

 

 

 

 

7874 (2400)

94%

96%

 

 

 

 

 

8530 (2600)

93%

95%

 

 

 

 

 

9186 (2800)

92%

94%

 

 

 

 

 

9843 (3000)

90%

92%

 

 

 

 

NOTES

 

 

 

1.This category of electronic equipment is agency rated for use in an atmosphere free of conductive particles. Some industrial facilities may require a room air filtration system to keep the UPS free of excess moisture and contaminants.

2.The UPS system is designed to operate continuously at 40°C. However, design equipment life expectancy will be extended with lower temperatures (25°C is recommended).

3.Ambient temperature is the maximum ambient temperature during any 24-hour period. For operation at higher ambient temperatures, consult your Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.

4.Exercise care during installation to ensure unimpeded airflow through the UPS system. For operation at higher elevations, consult your Liebert sales representative or call Liebert Global Services at 1-800-LIEBERT.

109

Image 115
Contents Liebert Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions Multi-Module UPS, 100-500kVA System DescriptionMulti-Module UPS, 500-750kVA Types of System Control Cabinets SCCs ReliabilityDesigned for Success Other Factors to Consider Safety PrecautionsInput Power Failure Modes of OperationOperator Controls 1989-2003 Options BatteryTwo Breaker Maintenance Bypass Battery Racks or CabinetsModule Battery Disconnect Three Breaker Maintenance BypassSystem Control Cabinet General Component DescriptionsUPS Module Battery PlantControls Hardware Detailed Component DescriptionsSoftware Input Circuit Breaker Input Power FactorRectifier/Charger OperationBattery Equalize Charge Circuit Battery Charging CircuitBattery Disconnect Battery Charge Current LimitingOutput Regulation and Overload Performance Non-Linear Load CharacteristicsUnbalanced Load Characteristics InverterFuse Protection Static BypassShorted SCR Monitoring Pulsed Parallel Operation Static Switch IsolationLoad Transfers Transfer and Retransfer Conditions Retransfer Inhibited Redundant ModeDisplay Screen and Operator Controls Features1000kVA 500kVADescription Function Operation Numbers are used as keys to data in , below Refer to 3.4.5 Shutdown ProceduresDescription Location Function Switches behind SCC control panel door Menu tree Menu Tree NavigationSCC Master Menu Master Menu ScreenModule Master Menu Operation Input Metering Displays SCC Monitor/Mimic Display ScreenOutput Metering Displays Item 6 System Status Messages Status/Alarm Message AreasItem 7 Alarm Messages Item 5 Module Status MessagesModule Monitor/Mimic display screen Module Monitor/Mimic Display ScreenItem 5 Alarm Messages Alarm MessagesModule Display SCC DisplayMonitor/Mimic display example Utility fail 2700kVAKVA//2170 KWkW 325A0A 325A0A 325A0A Upsinputpwr Battery MOD 1 OFF Line SUM ALM MVODLTS2 OFF540 Line SUM ALM Walk-in display screen during start-up Walk-In Display ScreenPresent Status Status Reports ScreensSCC Status Report Event HistoryModule Status Report History status report screens History StatusAlarm in SCC Alarm in Module Alarm conditions that freeze history data gatheringSystem Status Battery Cycle Monitor-Module OnlyBattery cycle monitoring summary screen SCC system configuration screen System Configuration ScreensDate screen DateTime screen TimeAuto Dial Auto dial setting screenMaximum Auto-Retransfer Attempts Modem Baud RateRetransfer Attempts System Current RatingLanguage Selection System OptionsContinuous Duty Static Switch Optional Battery test screen-MMU onlySCC and module remote monitor indications Remote MonitorModule alarm limit settings screen Alarm Limit Settings ScreenTemperature Limit Setting Optional Battery Float VoltageRefer to 3.4.3 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.4.1 SCC Start-Up Procedure for more details Start-Up Procedures ScreenModule start- up procedures screens Shutdown Procedures ScreenSCC shutdown procedures screen Battery time screen 15 minute discharge Battery Time Screen Module OnlyElapsed Time Minutes Upper Limit Actual Lower LimitOperation Meter calibration screen Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenSystem Status Messages Alarm and Status Messages Module Status MessagesLoad Block Messages Abbreviations used in alarm messagesAbbreviation Definition Alarm messages meaning and corrective action Control Power Manual ResetStatic Switch Bypass PhaseModule N Off Reverse PowerInverter Fault TransferNew Alarm Battery OvertempOvertemperature TimeoutAlarm Message Alarm messages summarySpecial Functions Requesting Information Communication InterfacesWorldwide Reporting Auto-DialLocal Reporting to a Monitor Local Reporting to a TerminalSite Reporting SiteScan or Snmp Remote Monitor Panel Liebert Series 610 terminal commandsSeparate / Simultaneous Outputs Circuit breaker abbreviations Abbreviation Circuit Breaker OK to Transfer Load on BypassLoad on bypass, UPS available Momentary Overloads Momentary overload, pulsed static bypass switchInput power fail-load on battery Input Power Failure-Load on BatteryOne module off-line, load on UPS One Module Off-LineLoad on UPS-battery not available Off BatteryEmergency Modules Off Refer to 3.4.5 Shutdown ProceduresEmergency power off Remote Emergency Power OffSystem Shutdown Refer to 3.3.10 Maintenance BypassLoad on maintenance bypass, two breakers SCC Start-Up Procedure Manual ProceduresRefer to 3.5 Automatic Operations for more details Operation Operation SCC start-up procedures screen UPS Module Start-Up Module start-up procedures screen Operation Manual Transfer Instructions UPS Lead Load Transfer ProceduresIf the load is on Maintenance Bypass Maintenance Bypass Load TransfersIf the load is on the UPS System Bypass Shutdown Procedures System Shutdown Procedure Module Shutdown Procedure Automatic Operations Remote Emergency Power Off RepoLocal Emergency Modules Off Lemo 150% Overloads Without TransferAutomatic Transfers to Bypass 1000%Automatic Module Off-Line Automatic Retransfers to UPSAutomatic Emergency Modules Off Maintenance Training Liebert Global ServicesMaintenance Agreements The Signature Program Professional Start-UpRecord Log Routine MaintenanceAir Filters Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalBattery voltage record Battery retorque valuesRack-Mounted Batteries Detection of Trouble Torque specifications unless otherwise labeledTorque Requirements Recommended Test Equipment Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Corrective ActionsRating Power factor pf KVAKVA Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Specifications 112 Page Locations
Related manuals
Manual 112 pages 3.63 Kb

Series 610 specifications

The Emerson Series 610 is a cutting-edge solution for precise process measurement and control, designed specifically for industries where accuracy and reliability are paramount. This advanced instrument, often utilized in oil and gas, chemical processing, and water treatment sectors, combines innovative technology with robust features to meet the demanding requirements of modern industrial applications.

One of the standout features of the Series 610 is its exceptional measurement accuracy. The device employs advanced sensor technology that enables precise determination of variables such as pressure, temperature, and flow. This accuracy translates into improved process efficiency and enhanced product quality. With a wide range of measurement capabilities, the Series 610 can handle varying process conditions and fluid types, making it versatile across different applications.

The heart of the Emerson Series 610 lies in its intelligent diagnostics and predictive maintenance functionalities. This built-in technology allows for real-time monitoring of the device's operational status, providing valuable insights into performance trends. By detecting anomalies early, users can take proactive measures to prevent potential failures, thereby reducing downtime and maintenance costs.

Moreover, the Series 610 is designed with user-friendly features. Its intuitive interface and easy-to-navigate menus facilitate quick setup and configuration, enabling operators to be productive from the outset. The device also supports various communication protocols, including HART and FOUNDATION fieldbus, ensuring seamless integration into existing control systems and enhancing overall automation capabilities.

Another notable characteristic of the Emerson Series 610 is its robust construction. Designed to withstand harsh environmental conditions, it is built with durable materials that offer high resistance to corrosion and physical damage. This durability ensures longevity and reliability, even in the most challenging industrial environments.

In summary, the Emerson Series 610 represents a significant advancement in process measurement technology. With its exceptional accuracy, intelligent diagnostics, user-friendly design, and robust construction, it is an ideal choice for industries seeking to enhance their operational efficiency and reliability. Its ability to seamlessly integrate into existing systems further solidifies its position as a leading solution in the field of industrial measurement and control. As industries continue to evolve, the Series 610 is poised to meet the challenges of the future with confidence and precision.