Emerson Series 610 manual Operation

Page 33

Operation

From any primary screen (accessed directly from the Master Menu), pushing the Select pad once will return you to the Master Menu. From any secondary screen, pushing the Select pad twice will return you to the Master Menu.

Please note that some screens have multiple pages. However, in each case, instructions appear for accessing other pages.

Monitor/Mimic Display—This graphic mimics the power flow through the UPS system. Input voltage and current readings, battery status, UPS ratings, load readings, circuit breaker indica- tions, system status and alarm messages are all displayed on this screen.

Walk-In Display (Modules Only)—This is a bar graph that shows DC bus voltage, input cur- rents and UPS module output voltage (all in percent of nominal). This screen typically is utilized during start-up procedures.

Status Reports—This display consists of four submenu selections: present status, event history, history status and system status. These screens display data on the system’s present and past performance. They also display information about any faults that have occurred in the system and total operating hours for the controls.

System Configuration—This screen displays the current configuration of the UPS system. It also enables the operator to reset the date, time and dial-out phone numbers. The SCC current rating can also be adjusted lower than design maximum. The operator can view, but cannot change, any of the settings unless the Interlock (Security Access) button is pressed.

Limit Settings—This security access display shows the present UPS system alarm limit set- tings. The operator can view the settings, but they should not be changed without consulting Lie- bert Global Services.

Load Transfer Procedures (SCC Only)—This screen specifies all of the steps required to man- ually transfer the critical load between the UPS system and the bypass source. Comparisons of the voltage, frequency and phase synchronization of the UPS system output and the bypass line are also illustrated to aid in the transfer or retransfer procedure.

Start-UpProcedures—This two-page screen lists step-by-step procedures to start the UPS sys- tem and the modules.

Shutdown Procedures—This two-page screen lists the proper sequence of steps to shutdown the UPS system and the modules for maintenance or repairs. The steps instruct the operator to transfer the critical load to bypass, open the battery circuit breakers and open the UPS module output and input circuit breakers to shut down and isolate the modules. The critical load will remain on bypass power unless circuit breakers outside the UPS system are also opened.

Battery Time (Modules Only)—This graph displays the projected battery voltage drop caused by a battery discharge over time. During a period of battery discharge, the Liebert Series 610 cal- culates the battery time remaining based on battery rating, initial battery condition and actual connected load. The UPS continues to update and display both rated (theoretical) and calculated time every 6 seconds. This enables the operator to immediately see the effects of load shedding on time remaining and to accurately assess his power resources.

Meter Calibration—This security access screen enables an authorized Liebert field-service engineer to adjust and calibrate the UPS metered functions. The operator can view, but should not change, any of the settings.

Battery Equalize—The battery equalize screen lets the operator change the battery equalize recharging mode from manual to automatic and to observe or change the equalize time. Battery equalize charge voltage is higher than battery float (constant) charge voltage. Automatic and manual equalizing can be controlled from the SCC, while only manual equalizing can be con- trolled from the module.

NOTE

Do not use battery equalize charging with sealed-cell batteries. Refer to the battery manufacturer’s manual, available on the manufacturer’s Web site, for specific information about equalize charging.

Customer Alarm Definitions (SCC Only)—This optional screen allows the operator to define alarms for conditions external to the UPS, battery or switchgear.

27

Image 33
Contents Liebert Series 610 UPS Battery Cabinet Precautions Table of Contents Specifications MaintenanceFigures Tables Important Safety Instructions Multi-Module UPS, 100-500kVA System DescriptionMulti-Module UPS, 500-750kVA Reliability Types of System Control Cabinets SCCsDesigned for Success Input Power Failure Safety PrecautionsModes of Operation Other Factors to ConsiderOperator Controls 1989-2003 Options BatteryModule Battery Disconnect Battery Racks or CabinetsThree Breaker Maintenance Bypass Two Breaker Maintenance BypassSystem Control Cabinet General Component DescriptionsUPS Module Battery PlantDetailed Component Descriptions Controls HardwareSoftware Rectifier/Charger Input Power FactorOperation Input Circuit BreakerBattery Disconnect Battery Charging CircuitBattery Charge Current Limiting Battery Equalize Charge CircuitUnbalanced Load Characteristics Non-Linear Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Bypass Fuse ProtectionShorted SCR Monitoring Static Switch Isolation Pulsed Parallel OperationLoad Transfers Transfer and Retransfer Conditions Retransfer Inhibited Redundant ModeDisplay Screen and Operator Controls Features500kVA 1000kVADescription Function Operation Refer to 3.4.5 Shutdown Procedures Numbers are used as keys to data in , belowDescription Location Function Switches behind SCC control panel door Menu tree Menu Tree NavigationMaster Menu Screen SCC Master MenuModule Master Menu Operation SCC Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Item 7 Alarm Messages Status/Alarm Message AreasItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic display screen Module Monitor/Mimic Display ScreenItem 5 Alarm Messages Alarm MessagesModule Display SCC DisplayMonitor/Mimic display example Utility fail 2700kVAKVA//2170 KWkW 325A0A 325A0A 325A0A Upsinputpwr Battery MOD 1 OFF Line SUM ALM MVODLTS2 OFF540 Line SUM ALM Walk-in display screen during start-up Walk-In Display ScreenPresent Status Status Reports ScreensEvent History SCC Status ReportModule Status Report History status report screens History StatusAlarm in SCC Alarm in Module Alarm conditions that freeze history data gatheringSystem Status Battery Cycle Monitor-Module OnlyBattery cycle monitoring summary screen SCC system configuration screen System Configuration ScreensDate screen DateTime screen TimeAuto Dial Auto dial setting screenMaximum Auto-Retransfer Attempts Modem Baud RateLanguage Selection System Current RatingSystem Options Retransfer AttemptsContinuous Duty Static Switch Optional Battery test screen-MMU onlySCC and module remote monitor indications Remote MonitorModule alarm limit settings screen Alarm Limit Settings ScreenTemperature Limit Setting Optional Battery Float VoltageRefer to 3.4.3 Load Transfer Procedures for more details Load Transfer Procedures ScreenRefer to 3.4.1 SCC Start-Up Procedure for more details Start-Up Procedures ScreenModule start- up procedures screens Shutdown Procedures ScreenSCC shutdown procedures screen Battery time screen 15 minute discharge Battery Time Screen Module OnlyElapsed Time Minutes Upper Limit Actual Lower LimitOperation Meter calibration screen Meter Calibration ScreenBattery equalize screen Battery Equalize ScreenSystem Status Messages Alarm and Status Messages Module Status MessagesAbbreviations used in alarm messages Load Block MessagesAbbreviation Definition Alarm messages meaning and corrective action Static Switch Manual ResetBypass Phase Control PowerInverter Fault Reverse PowerTransfer Module N OffOvertemperature Battery OvertempTimeout New AlarmAlarm messages summary Alarm MessageSpecial Functions Worldwide Reporting Communication InterfacesAuto-Dial Requesting InformationLocal Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Liebert Series 610 terminal commands Remote Monitor PanelSeparate / Simultaneous Outputs Circuit breaker abbreviations Abbreviation Circuit Breaker OK to Transfer Load on BypassLoad on bypass, UPS available Momentary Overloads Momentary overload, pulsed static bypass switchInput power fail-load on battery Input Power Failure-Load on BatteryOne module off-line, load on UPS One Module Off-LineLoad on UPS-battery not available Off BatteryEmergency Modules Off Refer to 3.4.5 Shutdown ProceduresEmergency power off Remote Emergency Power OffSystem Shutdown Refer to 3.3.10 Maintenance BypassLoad on maintenance bypass, two breakers Manual Procedures SCC Start-Up ProcedureRefer to 3.5 Automatic Operations for more details Operation Operation SCC start-up procedures screen UPS Module Start-Up Module start-up procedures screen Operation Manual Transfer Instructions UPS Lead Load Transfer ProceduresMaintenance Bypass Load Transfers If the load is on Maintenance BypassIf the load is on the UPS System Bypass Shutdown Procedures System Shutdown Procedure Module Shutdown Procedure Remote Emergency Power Off Repo Automatic OperationsLocal Emergency Modules Off Lemo Automatic Transfers to Bypass Overloads Without Transfer1000% 150%Automatic Retransfers to UPS Automatic Module Off-LineAutomatic Emergency Modules Off Maintenance Maintenance Agreements The Signature Program Liebert Global ServicesProfessional Start-Up TrainingRoutine Maintenance Record LogAir Filters Limited Life Components Battery Safety Precautions Battery MaintenanceAvertissement Number of Cells Battery Voltage VDC Nominal Float Matching Battery Cabinets OptionalBattery retorque values Battery voltage recordRack-Mounted Batteries Torque specifications unless otherwise labeled Detection of TroubleTorque Requirements Upstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemCorrective Actions Recommended Test EquipmentPower factor pf KVA RatingKVA Environmental Conditions Specifications applicable to environmentBattery Operation AdjustmentsElectrical Specifications Specifications 112 Page Locations
Related manuals
Manual 112 pages 3.63 Kb

Series 610 specifications

The Emerson Series 610 is a cutting-edge solution for precise process measurement and control, designed specifically for industries where accuracy and reliability are paramount. This advanced instrument, often utilized in oil and gas, chemical processing, and water treatment sectors, combines innovative technology with robust features to meet the demanding requirements of modern industrial applications.

One of the standout features of the Series 610 is its exceptional measurement accuracy. The device employs advanced sensor technology that enables precise determination of variables such as pressure, temperature, and flow. This accuracy translates into improved process efficiency and enhanced product quality. With a wide range of measurement capabilities, the Series 610 can handle varying process conditions and fluid types, making it versatile across different applications.

The heart of the Emerson Series 610 lies in its intelligent diagnostics and predictive maintenance functionalities. This built-in technology allows for real-time monitoring of the device's operational status, providing valuable insights into performance trends. By detecting anomalies early, users can take proactive measures to prevent potential failures, thereby reducing downtime and maintenance costs.

Moreover, the Series 610 is designed with user-friendly features. Its intuitive interface and easy-to-navigate menus facilitate quick setup and configuration, enabling operators to be productive from the outset. The device also supports various communication protocols, including HART and FOUNDATION fieldbus, ensuring seamless integration into existing control systems and enhancing overall automation capabilities.

Another notable characteristic of the Emerson Series 610 is its robust construction. Designed to withstand harsh environmental conditions, it is built with durable materials that offer high resistance to corrosion and physical damage. This durability ensures longevity and reliability, even in the most challenging industrial environments.

In summary, the Emerson Series 610 represents a significant advancement in process measurement technology. With its exceptional accuracy, intelligent diagnostics, user-friendly design, and robust construction, it is an ideal choice for industries seeking to enhance their operational efficiency and reliability. Its ability to seamlessly integrate into existing systems further solidifies its position as a leading solution in the field of industrial measurement and control. As industries continue to evolve, the Series 610 is poised to meet the challenges of the future with confidence and precision.