Emerson Series 610 manual Module Monitor/Mimic Display Screen, Module Monitor/Mimic display screen

Page 36

Operation

3.2.3Module Monitor/Mimic Display Screen

From module Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Select pad and the Monitor/Mimic screen is displayed.

The Monitor/Mimic display screen is a simplified block diagram of the UPS module and power connec- tions. This screen gives the operator an overall view of the power flow through the UPS module. The screen consists of three major sections: the input/UPS metering section, the load metering section and the status and alarm message areas. The metered parameter values on the Monitor/Mimic screen are updated at one second intervals.

Figure 15 Module Monitor/Mimic display screen

4

1

UPS INPUT PWR

A-B B-C C-A 480V 480V 480V 350A 350A 350A

2

BATTERY

VOLTS 540

AMPS 15 CHARG

NOTE

© 1989-2003

UPS RATINGS

AP648-84

RATED 400 KVA OUTPUT VOLTAGE

A-B B-C C-A 480V 480V 480V

60.0 Hz

3

5

LOAD

270 KVA / 217 KW

A B C 325A 325A 325A

All voltage readings are phase-to-phase measurements (A-B, B-C and C-A). All current readings are phase measurements (A, B and C).

Input Metering Displays

Item 1 - UPS Input Pwr: This block displays the UPS module input voltage and current. The Mod- ule Input breaker is shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.

Item 2 - Battery: The battery block displays the DC bus voltage and the charge or discharge current to or from the battery. This block reads MODULE DC BUS when the battery circuit breaker is open and BATTERY when the battery circuit breaker is closed during normal operation. This block reads BATTERY EQUALIZE when the battery equalize charge voltage is used to recharge the battery.

This block also shows BATTERY TEMPERATURE when the battery temperature sensor option is installed. The Module Battery Disconnect (MBD) is shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.

Output Metering Displays

Item 3 - UPS Ratings: The module part number and kVA rating are specified at the top of this block. The UPS output voltage and frequency are also displayed in this block. The Module Output breaker is shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.

Item 4 - Load: This block displays the module output power to the critical load in kVA and kW. The critical load current per phase is also displayed in this block.

30

Image 36
Contents Liebert Series 610 UPS Battery Cabinet Precautions Table of Contents Maintenance SpecificationsFigures Tables Important Safety Instructions System Description Multi-Module UPS, 100-500kVAMulti-Module UPS, 500-750kVA Reliability Types of System Control Cabinets SCCsDesigned for Success Safety Precautions Input Power FailureModes of Operation Other Factors to ConsiderOperator Controls 1989-2003 Battery OptionsBattery Racks or Cabinets Module Battery DisconnectThree Breaker Maintenance Bypass Two Breaker Maintenance BypassGeneral Component Descriptions System Control CabinetBattery Plant UPS ModuleDetailed Component Descriptions Controls HardwareSoftware Input Power Factor Rectifier/ChargerOperation Input Circuit BreakerBattery Charging Circuit Battery DisconnectBattery Charge Current Limiting Battery Equalize Charge CircuitNon-Linear Load Characteristics Unbalanced Load CharacteristicsInverter Output Regulation and Overload PerformanceStatic Bypass Fuse ProtectionShorted SCR Monitoring Static Switch Isolation Pulsed Parallel OperationLoad Transfers Transfer and Retransfer Conditions Redundant Mode Retransfer InhibitedFeatures Display Screen and Operator Controls500kVA 1000kVADescription Function Operation Refer to 3.4.5 Shutdown Procedures Numbers are used as keys to data in , belowDescription Location Function Switches behind SCC control panel door Menu Tree Navigation Menu treeMaster Menu Screen SCC Master MenuModule Master Menu Operation SCC Monitor/Mimic Display Screen Input Metering DisplaysOutput Metering Displays Status/Alarm Message Areas Item 7 Alarm MessagesItem 5 Module Status Messages Item 6 System Status MessagesModule Monitor/Mimic Display Screen Module Monitor/Mimic display screenAlarm Messages Item 5 Alarm MessagesSCC Display Module DisplayMonitor/Mimic display example Utility fail 2700kVAKVA//2170 KWkW 325A0A 325A0A 325A0A Upsinputpwr Battery MOD 1 OFF Line SUM ALM MVODLTS2 OFF540 Line SUM ALM Walk-In Display Screen Walk-in display screen during start-upStatus Reports Screens Present StatusEvent History SCC Status ReportModule Status Report History Status History status report screensAlarm conditions that freeze history data gathering Alarm in SCC Alarm in ModuleBattery Cycle Monitor-Module Only System StatusBattery cycle monitoring summary screen System Configuration Screens SCC system configuration screenDate Date screenTime Time screenAuto dial setting screen Auto DialModem Baud Rate Maximum Auto-Retransfer AttemptsSystem Current Rating Language SelectionSystem Options Retransfer AttemptsBattery test screen-MMU only Continuous Duty Static Switch OptionalRemote Monitor SCC and module remote monitor indicationsAlarm Limit Settings Screen Module alarm limit settings screenBattery Float Voltage Temperature Limit Setting OptionalLoad Transfer Procedures Screen Refer to 3.4.3 Load Transfer Procedures for more detailsStart-Up Procedures Screen Refer to 3.4.1 SCC Start-Up Procedure for more detailsShutdown Procedures Screen Module start- up procedures screensSCC shutdown procedures screen Battery Time Screen Module Only Battery time screen 15 minute dischargeUpper Limit Actual Lower Limit Elapsed Time MinutesOperation Meter Calibration Screen Meter calibration screenBattery Equalize Screen Battery equalize screenAlarm and Status Messages Module Status Messages System Status MessagesAbbreviations used in alarm messages Load Block MessagesAbbreviation Definition Alarm messages meaning and corrective action Manual Reset Static SwitchBypass Phase Control PowerReverse Power Inverter FaultTransfer Module N OffBattery Overtemp OvertemperatureTimeout New AlarmAlarm messages summary Alarm MessageSpecial Functions Communication Interfaces Worldwide ReportingAuto-Dial Requesting InformationLocal Reporting to a Terminal Local Reporting to a MonitorSite Reporting SiteScan or Snmp Liebert Series 610 terminal commands Remote Monitor PanelSeparate / Simultaneous Outputs Circuit breaker abbreviations Abbreviation Circuit Breaker Load on Bypass OK to TransferLoad on bypass, UPS available Momentary overload, pulsed static bypass switch Momentary OverloadsInput Power Failure-Load on Battery Input power fail-load on batteryOne Module Off-Line One module off-line, load on UPSOff Battery Load on UPS-battery not availableRefer to 3.4.5 Shutdown Procedures Emergency Modules OffRemote Emergency Power Off Emergency power offRefer to 3.3.10 Maintenance Bypass System ShutdownLoad on maintenance bypass, two breakers Manual Procedures SCC Start-Up ProcedureRefer to 3.5 Automatic Operations for more details Operation Operation SCC start-up procedures screen UPS Module Start-Up Module start-up procedures screen Operation Load Transfer Procedures Manual Transfer Instructions UPS LeadMaintenance Bypass Load Transfers If the load is on Maintenance BypassIf the load is on the UPS System Bypass Shutdown Procedures System Shutdown Procedure Module Shutdown Procedure Remote Emergency Power Off Repo Automatic OperationsLocal Emergency Modules Off Lemo Overloads Without Transfer Automatic Transfers to Bypass1000% 150%Automatic Retransfers to UPS Automatic Module Off-LineAutomatic Emergency Modules Off Maintenance Liebert Global Services Maintenance Agreements The Signature ProgramProfessional Start-Up TrainingRoutine Maintenance Record LogAir Filters Limited Life Components Battery Maintenance Battery Safety PrecautionsAvertissement Matching Battery Cabinets Optional Number of Cells Battery Voltage VDC Nominal FloatBattery retorque values Battery voltage recordRack-Mounted Batteries Torque specifications unless otherwise labeled Detection of TroubleTorque Requirements Reporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsCorrective Actions Recommended Test EquipmentPower factor pf KVA RatingKVA Specifications applicable to environment Environmental ConditionsAdjustments Battery OperationElectrical Specifications Specifications 112 Page Locations
Related manuals
Manual 112 pages 3.63 Kb

Series 610 specifications

The Emerson Series 610 is a cutting-edge solution for precise process measurement and control, designed specifically for industries where accuracy and reliability are paramount. This advanced instrument, often utilized in oil and gas, chemical processing, and water treatment sectors, combines innovative technology with robust features to meet the demanding requirements of modern industrial applications.

One of the standout features of the Series 610 is its exceptional measurement accuracy. The device employs advanced sensor technology that enables precise determination of variables such as pressure, temperature, and flow. This accuracy translates into improved process efficiency and enhanced product quality. With a wide range of measurement capabilities, the Series 610 can handle varying process conditions and fluid types, making it versatile across different applications.

The heart of the Emerson Series 610 lies in its intelligent diagnostics and predictive maintenance functionalities. This built-in technology allows for real-time monitoring of the device's operational status, providing valuable insights into performance trends. By detecting anomalies early, users can take proactive measures to prevent potential failures, thereby reducing downtime and maintenance costs.

Moreover, the Series 610 is designed with user-friendly features. Its intuitive interface and easy-to-navigate menus facilitate quick setup and configuration, enabling operators to be productive from the outset. The device also supports various communication protocols, including HART and FOUNDATION fieldbus, ensuring seamless integration into existing control systems and enhancing overall automation capabilities.

Another notable characteristic of the Emerson Series 610 is its robust construction. Designed to withstand harsh environmental conditions, it is built with durable materials that offer high resistance to corrosion and physical damage. This durability ensures longevity and reliability, even in the most challenging industrial environments.

In summary, the Emerson Series 610 represents a significant advancement in process measurement technology. With its exceptional accuracy, intelligent diagnostics, user-friendly design, and robust construction, it is an ideal choice for industries seeking to enhance their operational efficiency and reliability. Its ability to seamlessly integrate into existing systems further solidifies its position as a leading solution in the field of industrial measurement and control. As industries continue to evolve, the Series 610 is poised to meet the challenges of the future with confidence and precision.