Emerson instruction manual FM Intrinsically Safe Installation for Model 5081-T-FI

Page 38

32

MODEL

8

This document contains information proprietary to Rosemount Analytical, and is not to be made available

to those who may compete with Rosemount Analytical.

7

6

5

4

3

FISCO

FM INTRINSIC SAFETY INSTALLATION

 

 

2

1

 

 

 

 

REVISION

 

 

D

LTR

ECO

DESCRIPTION

BY

DATE

CHK

 

 

 

 

 

1400284

5081-T

D

APPROVED CONDUCTIVITY

SENSORS

222,225,226 & 228

242 (1" & 2" ONLY)

INFRARED

 

REMOTE CONTROL UNIT

 

(RMT PN 23572-00)

 

FOR USE IN

10

CLASS I AREA ONLY

MODEL

 

 

 

5081-T-FI

 

 

 

XMTR

8

9

10

7

6

 

 

11

5

 

 

12

4

 

 

13

3

 

 

14

2

 

 

15

1

 

 

16

HAZARDOUS (CLASSIFIED) LOCATIONS

IS CLASS I, II, III,

DIVISION 1,

GROUPS A, B, C, D, E, F, G;

NI CLASS I,

DIVISION 2,

GROUPS A,B,C,D;

SUITABLE CLASS II,

DIVISION 2,

GROUPS F & G;

SUITABLE CLASS III,

DIVISION 2

NON-HAZARDOUS LOCATIONS

ANY FM APPROVED

ANY FM APPROVED

ASSOCIATED

TERMINATOR

APPARATUS

ANY FM APPROVED

C

INTRINSICALLY SAFE

 

APPARATUS

 

C

10MAXIMUM SENSOR CABLE LENGTH IS 250 FEET.

9.USE SUPPLY WIRES SUITABLE FOR 5°C ABOVE SURROUNDING AMBIENT.

8.NO REVISION TO DRAWING WITHOUT PRIOR FACTORY MUTUAL RESEARCH APPROVAL.

7.THE CONFIGURATION OF ASSOCIATED APPARATUS MUST BE FACTORY MUTUAL RESEARCH APPROVED

BUNDER THE ASSOCIATED CONCEPT.

6.CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 Vrms OR Vdc.

5.ASSOCIATED APPARATUS MANUFACTURER'S INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.

4.THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS WITH ASSOCIATED APPARATUS WHEN THE FOLLOWING IS TRUE:

FIELD DEVICE INPUT

ASSOCIATED APPARATUS OUTPUT

Vmax OR Ui

Voc, Vt OR Uo;

Imax OR Ii

Isc, It OR Io;

Pmax OR Pi

Po;

3Ci+ 3Ccable;

Ca, Ct OR Co

3Li + 3Lcable.

La, Lt OR Lo; OR Lc/Rc (La/Ra OR Lo/Ro) AND Li/Ri (La/Ra OR Lo/Ro)

A3. RESISTANCE BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN 1.0 Ohm.

2. DUST-TIGHT CONDUIT SEAL MUST BE USED WHEN INSTALLED IN CLASS II AND CLASS III ENVIRONMENTS.

1.INSTALLATION SHOULD BE IN ACCORDANCE WITH ANSI/ISA RP12.06 "INSTALLATION OF INTRINSICALLY SAFE SYSTEMS

FOR HAZARDOUS (CLASSIFIED) LOCATIONS" (EXCEPT CHAPTER 5 FOR FISCO INSTALLATIONS) AND THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70) SECTIONS 504 AND 505.

NOTES: UNLESS OTHERWISE SPECIFIED

8

7

6

5

ANY FM APPROVED

TERMINATOR

WARNING- SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY OR

SUITABILITY FOR DIVISION 2.

WARNING- TO PREVENT IGNITION OF FLAMMABLE OR COMBUSTIBLE ATMOSPHERES,

DISCONNECT POWER BEFORE SERVICING.

 

 

 

 

 

 

 

 

 

 

 

THIS DOCUMENT IS

 

 

 

 

 

 

 

 

 

 

 

 

CERTIFIED BY

 

 

 

 

 

 

 

 

 

 

 

 

FM

REV B

 

 

 

 

 

 

 

 

 

 

 

 

 

REV

 

 

 

 

 

 

 

 

 

 

 

 

 

REV

B

 

 

 

 

 

 

 

 

 

 

 

 

REV

 

 

 

 

TABLE I

 

 

 

 

 

 

REV

 

 

 

 

 

 

 

 

 

 

 

REV

 

 

 

5081-T-FI FISCO PARAMETERS

 

 

 

 

 

REVISIONS NOT PERMITTED

 

 

 

 

 

 

 

 

W/O AGENCY APPROVAL

 

 

SUPPLY / SIGNAL TERMINALS TB 1-15, 16

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL NO.

GROUPS

Vmax (Vdc)

Imax (mA)

Pmax (W)

Ci (nF)

Li (uH)

 

 

 

5081-T-FI

IIB/

17.5

 

380

5.32

 

 

5

10

 

 

 

C,D,E,F,G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5081-T-FI

IIC/

17.5

 

360

2.52

 

 

5

10

 

 

 

 

A,B,C,D,E,F,G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNLESS OTHERWISE SPECIFIED

ITEM

PART NO.

 

 

DESCRIPTION

 

QTY

 

 

 

 

 

TOLERANCES

 

 

 

 

BILL OF MATERIAL

 

 

 

 

.XX

+

.030

ANGLES + 1/2

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

.XXX

+

.010

-

 

 

 

 

 

 

 

 

 

 

-

 

APPROVALS

 

DATE

Uniloc

Rosemount Analytical,

 

 

 

 

 

DIMENSIONS ARE IN INCHES

 

 

 

 

 

 

 

 

 

 

Uniloc Division

 

 

 

 

 

REMOVE BURRS & SHARP EDGES .020 MAX

 

 

 

 

Irvine, CA 92606

 

 

 

 

 

 

 

DRAWN

 

 

 

 

2400 Barranca Pkwy

A

 

 

 

 

MACHINED FILLET RADII .020 MAX

B. JOHNSON

5/3/04

TITLE

 

 

 

 

 

 

NOMINAL SURFACE FINISH 125

 

 

 

 

MATERIAL

 

CHECKED J. FLOCK

 

5/6/04

SCHEMATIC, INSTALLATION

 

 

 

 

 

 

 

 

 

5081-T-FI XMTR

 

 

 

 

 

 

 

PROJECT

J. FLOCK

 

 

 

 

 

 

 

 

 

 

 

5/6/04

 

FM APPROVALS

 

 

 

 

 

 

 

ENGR APVD

 

 

 

5-6-04

 

FINISH

 

 

 

THIS DWG CREATED IN

DWG NO.

 

 

REV

8933

B

 

 

 

SOLID EDGE

 

 

D

1400284

 

B

RELEASE DATE

 

 

 

 

 

 

 

SIZE

 

ECO NO.

REV

 

3

 

 

 

 

 

SCALE NONE

TYPE

SHEET 1 OF

1

4

 

 

 

 

 

 

 

2

 

 

1

10-96

 

 

 

 

 

 

 

 

 

 

SECTION 4.0 INTRINSICALLY SAFE & EXPLOSION PROOF

FIGURE 4-15. FM Intrinsically Safe Installation for Model 5081-T-FI

Image 38
Contents Model 5081-T Essential Instructions Rev. Level DateModel 5081-T Table of Contents CONT’D Iii List of FiguresNumber Title List of Figures CONT’D List of TablesSection Description and Specifications Simple Menu StructureHart Recommended Ranges for Toroidal Sensors Recommended SensorsAtex I T N E X T Transmitter Display During Calibration and ProgrammingOverview of Hart Communication Hart Interface DevicesFoundation Fieldbus AMS Main Menu Tools Unpacking and Inspection Section InstallationMechanical Installation Orienting the Display BoardMounting on a Flat Surface 40308103 Pipe MountingModel 5081-T Sensor Selection Inductive LoopsSensor Selection Recommended SensorsPower Supply-Current Loop Wiring Power SUPPLY/CURRENT LoopPower Supply and Load Requirements. Refer to Figure Model 5081-T-HTPower Supply Wiring for Model 5081-T-FF/FI Typical Fieldbus Network Electrical Wiring ConfigurationSensor Wiring Section WiringSensor Wiring Electrical Installation Wiring Through a Junction BOXPower Wiring Model 5081-T-HT Power Wiring Model 5081-T-FFElectrical Installation Wiring Model 242 sensor to Model 5081-T transmitterSection Section IRC Infrared Remote Control Section Intrinsically Safe & Explosion ProofFM Explosion-Proof Installation for Model 5081-T-HT FM Intrinsically Safe Installation for Model 5081-T-HT CSA Intrinsically Safe Installation for Model 5081-T-HT Atex Intrisically Safe Label for Model 5081-T-HT Atex Intrisically Safe Label for Model 5081-T-HT FM Explosion-Proof Installation for Model 5081-T-FF FM Intrinsically Safe Installation for Model 5081-T-FF 10. CSA Intrinsically Safe Installation for Model 5081-T-FF 11. Atex Intrisically Safe Label for Model 5081-T-FF 12. Atex Intrinsically Safe Installation for Model 5081-T-FF FI-T 9241515-01 15. FM Intrinsically Safe Installation for Model 5081-T-FI 9241516-01 17. CSA Intrinsically Safe Installation for Model 5081-T-FI 18. Atex Intrisically Safe Label for Model 5081-T-FI 19. Atex Intrinsically Safe Installation for Model 5081-T-FI S U Section Display and OperationDisplays I T N E X TInfrared Remote Controller IRC KEY Functions Infrared Remote ControllerTo reset transmiter to factory default settings Quick Start for Model 5081-T-HT HartQuick Start for Model 5081-T-FF/FI Foundation Fieldbus Process Display Menu Tree Conductivity25.0C 12.00mA Calibration ProgramProgram Menu Mnemonics Diagnostic Messages Default SettingsDefault Settings for Model 5081-T-HT Entering the Security Code Using HoldSecurity Retrieving a Lost Security CodeAccessing the Calibrate Menu Section START-UP and CalibrationCalibrate Menu Model 5081-T-FFTemp Slope Procedure9URU Output CalGM!91 5ES-U1U17!91 U91Model 5081-T-HT Model 5081-T-FF Section ProgramingGeneral Definitions Output 5081-HT onlyPurpose 4QG Procedure9VUVU UhtuU7-P Process temperature is. Press Enter to saveTemp HCL DisplayG5-A H2SO4LHart GgshttSHI Setup CustPVO!RUT!!% 8VO!UTRange DefaultSetting Measurement Range Over Range Warning Limit G12-USection Foundation Fieldbus Operation PIDConnecting the Communicator Section Operation with ModelOff-line and On-line Operation Making Hart related settings from the keypadOperation PV LRV PV URV C/T-HT HART/Model 375 Menu Tree 1LSL USL C/T-HT HART/Model 375 Menu Tree 2LRV URV AO1PV AO PV LRV PV URV C/T-HT HART/Model 375 Menu Tree 4Limnotify Resource FaultstateBlockerr Featuresel Rsstate Faultstate MaxnotifyBlockerr AlarmhysStrev TagdescLowcut Alertkey HihilimPvftime Strev Statusopts StrategyLololim LolimLolopri IooptsSphilim Splolim ResetRate Reset Bkcalhys FfgainBaltime BypassStrev Rate Tagdesc ControloptsSphilim Alertkey OuthilimDvhipri DvlopriC/T-FF/FI Model 375 Menu Tree 9 C/T-FF/FI Model 375 Menu Tree 10 Current Operating Menu Section Diagnosis and TroubleshootingOverview 4DSG DLSTqiu IdvnutNON- Disabling Warnings Fault ConditionsDisabling Faults 9IITHU!1SS 9WHS!S-PJ1Hssqs Symptom Action Quick Troubleshooting GuideQuick Troubleshooting Guide Field TroubleshootingSystematic Troubleshooting Troubleshooting Flow ChartExample RTD Resistance ValuesFormula RTD Resistance ValuesWhen a Warning condition exists When a Fault existsTemp LO Troubleshooting When a Fault or Warning Message is ShowingTemp HI CPU FailRtd FAIL, Temp HI, and Temp LO CPU Fail and ROM Fail Transmitter Maintenance Section MaintenancePreventative Maintenance 0 C 2 1 0 % mAReplacement Parts for Model 5081-T Transmitter Exploded View of Model 5081-T TransmitterHart Communication Section Theory of OperationConductivity Output LogicSection Return of Material Warranty RepairNON-WARRANTY Repair GeneralThis page intentionally left blank Warranty Return of MaterialSpecifications subject to change without notice