If Utility Power is Available
If Utility Power is Available
The following fault conditions may arise when utility power is available.
Table 3-3 Possible Problems if Utility Power is Available
Problem | Probable Cause | Solution |
|
|
|
Display is OFF, AC is | Inverter is turned OFF. | AC output is always available when |
available on both hardwire |
| AC input is available. Under this |
and unit AC socket |
| condition, the inverter will not back |
|
| up the power when utility power is |
|
| OFF. |
|
|
|
Display is OFF, AC is not | Main AC Panel or AC generator | Check utility or generator output |
available on both hardwire | input is beyond the operating range of | voltage. |
and unit AC socket | the unit (103 to 132 Vac). |
|
|
|
|
Display is ON, AC is not | The 15A input circuit breaker on the | Reset the 15 A input circuit breaker. |
available on both hardwire | Main AC Panel or AC generator is |
|
and unit AC socket | tripped or turned OFF. | Reset the 15A supplemental protector |
| The 15 A circuit breaker on AC | |
| near the four AC outlets on the front | |
| Distribution Panel and 15 A | panel and reset the 15A circuit |
| supplementary protector near the four | breaker on the AC Distribution Panel |
| AC outlets on the front panel have |
|
| tripped. |
|
|
|
|
Display is ON, AC is | 15 A supplementary protector on the | Press the reset button to reset the |
available on hardwire | front panel has tripped. | circuit breaker. |
output but not on unit |
|
|
AC socket |
|
|
|
|
|
Bypass LED is flashing | During the first 20 seconds of transfer | None. |
| from inverter to Bypass Mode, the |
|
| inverter continuous to run and the |
|
| Bypass LED flashes. This provides |
|
| time for the utility to get steady |
|
| before it switches over. During the 20 |
|
| seconds delay time, the display |
|
| feature is frozen. |
|
|
|
|