Installation
Load Connection
7.5V to 100 V Models The 7.5 V to 100 V models are equipped with output bus bars. To make a typical load connection to a 7.5 V, 300 A power supply:
1.Strip the ends of the wires.
2.Remove the top part of the output cover. Do not remove the
3.Loosen wire clamp screws (part of strain relief). Do not disassemble the strain relief.
4.Insert load wire in strain relief.
5.Install connectors to load wiring.
6.Fasten connectors to bus bars with 5/16 in. x 5/8 in. (M8 x 16 mm) screws, 5/16 in. (M8) flat washers, lock washers, and hex nuts as shown in Figure 2.5.
7.Tighten the strain relief clamp.
8.Replace the top cover.
Note: Bus bar hole sizes are one of 0.343 in. (8.7 mm) D; two of 0.197 in. (5.0 mm) D.
Hex Nut (2 places)
Lock Washer (2 places)
Flat Washer (2 places)
Screw (2 places)
Wire connector (2 places)
Assembled View
Figure 2.5 Typical Load Connection Hardware
(For 7.5 V to 100 V models.)
48 | Operating Manual for XFR 2.8kW Series Power Supply |