Xantrex Technology XFR 2800 manual Using Remote Sensing

Page 57

Installation

Local and Remote Sensing

Using

Remote

Sensing

WARNING

There is a potential shock hazard at the sense points when using a power supply with a rated output greater than 40 V. Ensure that connections at the load end are shielded to prevent contact with hazardous voltages.

WARNING

Ensure that the chassis ground screw does not penetrate more than 3/8 in. (9 mm) into the rear panel of the unit.

CAUTION

Ground the sense line shield in one place only. Locations include: the power supply’s return output connection at the load, the power supply’s return output at its negative output terminal, or the power supply's chassis.

CAUTION

Do not use remote sensing with multiple supplies connected in series.

Use remote sensing during voltage mode operation to shift the power supply’s regulation point from its default position at the rear panel output terminals to the load or distribution terminals by using a separate pair of wires to allow the control circuitry to monitor the load voltage. This allows the power supply to compensate for voltage losses in the load lines which will otherwise degrade the regulation of the supply. Line drop is subtracted from the voltage available at the power supply's output.

To connect remote sense lines:

1.Turn OFF the power supply.

2.Remove the local sense jumpers connecting J10 mating connector terminal 5 (positive sense) to terminal 4 (positive output) and terminal 1 (return sense) to terminal 2 (power supply return).

3.Connect the positive remote sense lead to J10 mating connector terminal 5 (positive sense) and the negative lead to terminal 1 (return sense). Ensure that the mating connector is plugged securely into the rear panel sense connector. Connect the other ends of the sense wires to the corresponding sense points at the load.

Release 2.1

55

Image 57
Contents XFR 2800 Watt Series Programmable DC Power Supply Page XFR 2800 Watt Series What does this warranty cover and how long does it last? How do you get service?What will Xantrex do? Phone 604 422 Toll Free North America 800 667 Fax 604 421What does this warranty not cover? Disclaimer Product Model Number Serial Number Purchased From Purchase Date Information About Your Power SupplyPower Supply Safety Who Should Use This Manual Main SectionsManual Revisions About This Manual Power Supply Safety MarkingsContents Calibration Section Local Operation RemoteList of Figures List of Figures List of Tables List of Tables Features and Options DescriptionModel Voltage Range Current Range Features and Specifications Front Panel Controls Power Supply Front PanelRear Panel Connectors and Switch Power Supply Rear Panel Shows the functions assigned to each SW1 switch HIGH=OFF HIGH=ON Switch Function Open ClosedProgramming and Monitoring J2 Connector Vrmt Connector Reference Name FunctionMaking J2 Connections WiringSpecifications Models 300 12-220 20-130 33-85 40-70 Features and Specifications Models 60-46 100-28 150-18 300-9 600-4 Features and Specifications Input Conditions Additional SpecificationsRemote Programming Monitoring Additional FeaturesEnvironmental Specifications Output Connector Mechanical SpecificationsDimensional Drawings Basic Setup Procedure IntroductionStep # Description Action Reference Initial Inspection Periodic Cleaning Inspection, Cleaning, and PackagingReturning Power Supplies to the Manufacturer Shipping or Storage Carton Label Packaging for Shipping or StorageRack Mounting Location, Mounting, and VentilationAC Input Connector Voltage Selection AC Input PowerAC Input AC Voltage Range FrequencyWire Size Ratings Cable Outside Diameter AC Input Wire ConnectionAC Input Cover and Strain Relief Power-on Check Voltage Mode Operation CheckFunctional Tests Equipment RequiredCurrent Mode Operation Check Front Panel Function Checks Load Wiring Wire Size Maximum Current aLoad Connection Making Load Connections Maximum Load Wire Length for 1 V Line DropOutput Strain Relief and Cover Typical Load Connection Hardware To 600 V Models Output Voltage ConnectorSingle Load with Local Sensing Default Multiple Loads with Local Sensing 10Multiple Loads with Remote Sensing Local and Remote Sensing Sense WiringTerminal Name Function 11J10 Sense ConnectorUsing Remote Sensing 12 shows a sample setup for using remote sensing Operating Modes Automatic Crossover Standard OperationStandard Operation Local OperationConfiguration ShippedMode Setting Output Voltage Current Limit OVP Using Over Voltage Protection OVPResetting the OVP Circuit Controlling Shutdown Function via Connector Using the Shutdown FunctionLED Configuring Multiple Supplies for Series Operation Using Multiple SuppliesConfiguring ParallelSupplies for Parallel Operation of Multiple Supplies Supplies for Split Supply OperationSplit Supply Operation of Multiple Supplies Positive-negative SupplyLocal Operation Switch SW1-8 OTP Shutdown Selection Description Over Temperature Protection OTPEmergency Shutdown User DiagnosticsUnusual or Erratic Operation Abbreviated References Used in TableSymptom Check Further Checks and Corrections Remote Operation Options Remote Analog Programming ProcedureRemote Operation Control Programming ScalesRemote Operation Power Supply Settings for Different Programming Sources Connecting Programming Sources to J2 Connector Remote Monitoring of Output Voltage and Current Service Calibration SetupPrecautions EnvironmentAccessing Calibration Potentiometers Programming and Monitoring Calibration Locations Voltage Programming Circuit Calibration Calibrating for Programming AccuracyCurrent Limit Programming Circuit Calibration Output Voltage Monitor Circuit Calibration Calibrating for Readback AccuracyOutput Current Monitor Circuit Calibration Calibration Page Xantrex Technology Inc