IBM DCS9550 1S1 manual Thermal Alarm, Thermal Shutdown, Drive Carrier Module Faults

Page 59

Troubleshooting and Problem Solving

4.5.4Thermal Alarm

 

Symptom

Cause

 

Action

 

 

 

 

 

1

Ops Panel FAULT

If the internal

1

Check local ambient environment

 

LED AMBER.

temperature measured in

 

temperature is below the upper 40°C

2

An AMBER LED on

the airflow through the

 

specification.

enclosure exceeds a pre-

2

Check the installation for any airflow

 

one or more Power

set threshold a thermal

 

Supply/Cooling

alarm will sound.

 

restrictions at either the front or rear

 

Modules.

 

 

of the enclosure. A minimum gap of

 

 

 

 

25mm at the front and 50mm at the

3

Audible Alarm

 

 

rear is recommended.

 

Sounding.

 

 

 

4

Air temperature

 

3

Check for restrictions due to dust

 

 

build-up, clean as appropriate.

 

exiting PSU above

 

 

 

 

55°C.

 

4

Check for excessive re-circulation of

 

 

 

 

heated air from rear to the front, use

 

 

 

 

in a fully enclosed rack installation is

 

 

 

 

not recommended.

 

 

 

5

If possible shutdown the enclosure

 

 

 

 

and investigate the problem before

 

 

 

 

continuing.

 

 

 

 

 

4.5.5Thermal Shutdown

Important For thermal warnings please refer to the SES specification.

An Enclosure will shut down when a critical temperature threshold is exceeded in order to prevent permanent damage to the disk drives.

4.6Drive Carrier Module Faults

Disk drive status is monitored by a Green LED and an Amber LED mounted on the front of each Drive Carrier Module, providing the following indications:

Table 4–4LED Functions

State

Green

Amber

 

 

 

No drive fitted

Off

Off

 

 

 

Drive Power ON

On

Off

 

 

 

Drive Activity

On/Blink off

Off

 

 

 

Drive Fault

On

On

 

 

 

Drive activity - LED may be off for a length of time during power up.

44

IBM System Storage DCS9550 1S1 Storage Expansion Unit Installation, Service, and User Guide

Image 59
Contents IBM System Storage Page Preface International Standards Safety Guidelines Figure P-3PSU/Cooling Module Caution Label Figure P-5 PSU Safety Label Electric Shock Hazard Inside Class 1 Laser Product Avis de conformité à la réglementation d’Industrie Canada ESD Precautions Data Security Taiwan Contact Information How to Send Your Comments Page Page Contents Xiii IBM System Storage DCS9550 1S1 Storage Expansion Unit Introduction2Enclosure Chassis Front Enclosure ChassisMultiple Power Supply/Cooling Modules Power Supply/Cooling ModuleOperators Panel Ops Panel Indicators and SwitchesSCM Input/Output Module DCS9550 Controller Settings6SCM I/O Module 7SCM Front Panel as viewed from rear of Enclosure Sata Dual Path Transition Card Drive Status IndicatorsDrive Carrier Module Blank Modules Anti-tamper LocksDummy Carrier Modules PSU Safety and EMC Compliance DimensionsWeight AC Power 450W PSUAirflow EnvironmentInterfaces SCM I/O Module SpecificationDrive Carrier Module Specification Software Enclosure Services SES Support This page is intentionally blank Planning Your Installation Installation1Module locations Enclosure Bay Numbering ConventionRack Mounting Rail Kit Enclosure Installation ProceduresChassis Installation Parts Check List Pre-RequisitesPower Supply/Cooling Module Procedure ProcedurePower Supply/Cooling Module Installation 2AC Power Supply/Cooling Module Handle in Open Position FC-AL Interface SCM I/O Module ConfigurationsInternal Loop Structures Unit 1-S Unit 2- S 7IBM System Storage DCS9550 Couplet Cabling SCM I/O Module InstallationDrive Enclosure Device Addressing Switch Function Recommended Definition Number SettingSwitch Function Recommended Row Column Drive ConfigurationDrive Carrier Installation Parts Check List 10Installing a Sata Drive Carrier Module Activating the Locks Engaging the Anti-tamper Locks13Activating the Anti-tamper Lock Power Cord Connection Parts Check ListGrounding Checks This page is intentionally blank Operation Power OnAC PSU Power Supply/Cooling Module LEDsLED Ops Panel LEDsDisk Drives LEDs Power DownStarting the Drives Emulation Limitations Initial Start-up Problems Faulty CordsLEDs Alarm Sounds On Power UpGreen Signal Good LED on SCM Not Lit Ops Panel LED SCM I/O Module LEDs Audible AlarmAudible Alarm Mute Power Supply/Cooling Faults TroubleshootingSystem Faults Thermal Control Power supplies FittedThermal Shutdown Thermal AlarmDrive Carrier Module Faults Replacing a Module Dealing with Hardware FaultsContinuous Operation During Replacement Inserting the Module 2Removing/Inserting an AC Power Supply/Cooling Module Removing the Module SCM I/O Module5Removing an SCM I/O Module 7SCM I/O Module Latch Operation Removal and ReplacementSpare Parts and Ancillary Items IBM MTM 1269-1S1 Sata Disk Chassis FRUsThis page is intentionally blank Glossary Page Index System LED For additional information, visit the web at Trademarks Page Page Readers’ Comments We’d Like to Hear from You Business Reply Mail Page SC30-9738-00