Cisco Systems IGX 8400 Series manual Connecting a UVM to T1 Lines

Page 18

Installing Voice Cards

The total delay for a connection is defined as the sum of the propagation and trunk queuing delays. The total delay for a connection cannot be more than 25 ms different from the total delay for any other connection on the same card. The user is responsible for configuring the connections so that no difference between total delays exceeds 25 ms. If the 25 ms is exceeded, an error message is generated in the form CC0700d6, where CC is the slot number.

In System Software 8.2, add the connection with addcon using 7/8 coding even though the system internally uses 8/8 coding. This causes the system to reserve the additional bandwidth required for the TDM Transport feature.

Connecting a UVM to T1 Lines

Voice or data connections on a T1 line use the UVM front card and the BC-UVI-2T1EC back card. The procedure for connecting the T1 lines is as follows:

Step 1 Bring each cable through the opening at the bottom of the cabinet (if applicable) and up the back of the unit. Install optional Y-cables as needed. You can use the cable management feature to help route the cables.

Step 2 If the intended compression for voice channels is LDCELP and the number of channels on a T1 line exceeds 16, install cabling for pass-through. Note that the UVM does not pass-through t-type or td-type connections. For the steps that follow, refer to Figure 3-8for an illustration of the possible UVM cabling arrangements. Note that, in Example B, the number of channels has not exceeded the UVM capacity, so pass-through is unnecessary.

On port 1 of the primary UVM, connect the cable to the CPE.

On port 2 of the primary UVM, connect the cable to port 2.

Connect the cable from port 2 of the primary card to either port 1 or port 2 of the secondary UVM. Typically, if the secondary UVM is supporting the passed-through channels from only one primary UVM, you would connect the cable from port 2 of the primary card to port 1 of the secondary card. However, because the secondary UVM can receive 16 passed-through channels with LDCELP compression, you can pass 8 channels each from other UVMs.

If the secondary UVM is supporting an additional 8 channels with LDCELP, connect the cable between the port 2 of the secondary UVM and the other primary UVM.

For a description of the pass-through feature, refer to the Cisco IGX 8400 Series Reference.

Record the back slot number and port number of each line. These numbers are necessary for configuring the system after you complete hardware installation.

3-18Cisco IGX 8400 Series Installation and Configuration

Image 18
Contents Card Installation and Node Startup Preparing the CardsPreparing the Cards IGX 8410 Cards, Front View IGX 8410 Cards, Back View IGX 8420 Card Shelf, Front View IGX 8430 Back View Inserting the Cards Inserting ModulesMaking Signal Connections HssiConnecting Trunks Setting Up a UXM-EBringing Up a UXM-E Trunk Cable Management Inverse Multiplexing over ATM on Trunks DspcdsAdding an IMA Feeder Trunk Adding Links to an IMA Feeder GroupUXM-E Inverse Multiplexing ATM IMA Lines Removing Links from an IMA Feeder GroupConnecting an NTM T1 or Y1 Trunk Connecting an NTM E1 or Subrate TrunkBringing Up a UXM-E in UNI or NNI Port Mode Installing Voice Cards Connecting a CVM to a T1 or J1 LineConnecting a CVM to an E1 Line or a Subrate Trunk TDM Transport on the CVMConnecting a UVM to T1 Lines Pass-Through and Standard External UVM T1 Cabling Connecting a UVM to E1 Lines Pass-Through and Standard External UVM E1 Cabling Connecting a UVM to J1 Lines 10 Pass-Through and Standard External UVM J1 Cabling Making Serial Data Connections 11 SDI and LDI FaceplatesConfiguring the Port Modes of the HDM Back Cards Configuring the Mode of an LDI Port HDM and LDM Redundancy13 Connecting a DTE or DCE Adapter Cable to an LDI Making Frame Relay Connections Maximum Connections Per Port with Signalling ProtocolsSetting Up Frame Relay on a UFM Cable Redundancy on the UFMs14 Y-Cable Redundancy with Single and Dual-Port Cabling Connecting UFM Cabling Setting Up Frame Relay Ports and Connections UFMSetting Up Frame Relay on an FRM Commands for T1/E1 Frame RelayDeleting a Frame Relay Port Port Mode Selection for V.35 15 Setting the Port Mode DTE/DCE on an FRI Frame Relay Card RedundancySetting Up Frame Relay Ports and Connections FRM Making Alarm Relay Output Connections 36Cisco IGX 8400 Series Installation and Configuration Connecting a Single Network Management Station Making External Clock ConnectionsAttaching Peripherals 16 Connecting the Control Terminal LAN Connection for the Network Management Station 17 LAN Connection to SCMConfiguring the LAN Port D2.cb1 LAN superuser IGX 42Cisco IGX 8400 Series Installation and Configuration Connecting a Network Management Station to Multiple Networks Connecting the Printer 20 Connecting a Network PrinterConnecting a Modem 21 Connecting Modems to an IGX NodeConnecting the Power Supply Monitor Initial Startup of the IGXNPM Startup Diagnostic Test Fail screen looks like thisCard Self Test Inspecting Status LightsChecking the Power Supplies AC Systems IGX Configuration Summary50Cisco IGX 8400 Series Installation and Configuration Configuring an IGX Switch to Be an Interface Shelf Interworking Connections in a Tiered NetworkAdding Connections in a Tiered Network through the CLI Converting a Routing Node to an Interface Shelf