Power ON/OFF (5kVA models only)
1.Configure your UPS’s input and output: Put your UPS power module into setup mode by holding down both of its scroll buttons ( A and B ) at once. Scroll through the setup options (using A or B ) and select the appropriate setting for each of the following options using the “SELECT” button B .
•Input & Output Voltage: Select 200, 208 or 240 VAC.
•Output Frequency: Your UPS will autoselect 50 or 60 Hz to match the input.
•Economy Mode: Your UPS can provide
•After you have set these options, “exit” the setup mode with the scroll button A , then exit bypass mode by holding the ON button C down until you hear a beep.
2.Turn input to the UPS ON: Press and hold the power module's ON button C until you hear a beep to start your UPS in ON BATTERY mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the ini- tial load on the UPS. Your UPS will perform a brief
3.To turn the UPS power module and transformer module (if used) OFF: Press the power module's OFF button F until you hear a beep. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display D will show BYPASS MODE. Turn the power module's Output Breaker E OFF. Unplug the power module's AC input cord from the wall outlet. If a transformer module is used, unplug its connector cable from the power module. Your load will no longer be energized, and the LCD Display D will be dark.
E |
5kVA Models
|
|
| D |
C | A | B | F |
5kVA Models (Front Panel)