D.Audible Alarm Reset: The UPS shall provide an audible alarm that can be stopped using the user interface. If a new alarm is sensed after the original alarm has been silenced, it will reactivate the audible alarm.

E.Remote Emergency Power Off (REPO): The UPS shall be equipped with provisions for remote emergency power off and dry contact input that can be used to command UPS shut down remotely. Activation of this command shall lead to the following actions:

ƒinverter shutdown

ƒopening of the static bypass switch and the battery circuit breaker

ƒopening of an isolated dry contact on the programmable relay board

F.DB-9 Connector: One DB-9 connector with serial output will be provided for field diagnostics.

G.Dry Contacts: The UPS shall be provided standard with a programmable input/output relay board. This board shall have 8 dry contacts, i.e., 6 for input signals and 2 for output signals.Contacts shall be programmed as:

ƒUPS on Line

ƒLoad on Bypass

ƒUPS on Battery

ƒUPS Battery Low

ƒGeneral alarm

ƒBattery Fault

ƒRemote UPS on (input)

ƒRemote UPS off (input)

The contacts will be normally open and will change state to indicate the operating status. The contacts will be rated at 2.0 A (250 VAC / 30 VDC).

3.1MECHANICAL DESIGN AND VENTILATION

A.Enclosure: The UPS shall be housed in a freestanding enclosure with dead front construction. The mechanical structure of the UPS shall be sufficiently strong and rigid to withstand handling and installation operations without risk. The sheet-metal elements in the structure shall be protected against corrosion by a suitable treatment, such as zinc electroplating, bichromating, epoxy paint or an equivalent.

B.Cable Access: The standard UPS available shall accommodate bottom entry cables (top optional).

C.

Cabinet Weights and Dimensions: The width of the UPS is

[

]

(in inches) and has a

 

maximum weight of

[

]

(in lbs).

 

 

 

 

 

D.

Ventilation and Heat Rejection: The UPS shall be designed for forced air-cooling. Air inlets

 

shall be provided from the front bottom of the UPS enclosure. Air exhaust shall be from the top

 

portion of the unit. Full load heat rejection is

[

]

BTU /hour.

 

 

APC – MGE Galaxy 5000 Specification (60Hz) 10

Effective: June 1, 2008 REV X0 JJG

Parallel Module

 

Image 10
Contents Standards MGE GalaxyGeneral Summary SubmittalsQualifications & Quality Assurance TemperatureFinal Submittals DELIVERY, STORAGE, and HandlingService and Spare Parts WarrantyMAINTENANCE, Accessibility and Self Diagnostics System Description AC Input CharacteristicsAC Output Characteristics UPS Design RequirementsModes of Operation BatteryPFC Rectifier and Battery Charger Component DescriptionInverter Static Bypass 100% Rated, Continuous DutySystem Controls and Indicators Output Static Switch 100% Rated, Continuous DutyMeasurements Status Indications and Events Cabinet Weights and Dimensions The width of the UPS is Mechanical Design and VentilationOptional Accessories BatteryExternal Control and Communications Devices Page Maintenance & Service Contracts Maintenance TrainingSpare Parts END of Section 111 150 182 Configuration Battery 100 130 KVA40 KVA 50 KVA 60 KVA 80 KVA 100 130 120 15680 KVA 100 KVA 130 KVA Entry BatteryWeight 109 137 164 219 273 355300 lbs 700 lbs