Schneider Electric 5000 specifications

Page 12

2.RS232 or RS485 JBus/Modbus Card (66061): The U-Talk protocol shall be used with Solution-Pac 2 for remote monitoring or graceful shutdown for most popular file servers. The JBus protocol is used with third party Building Management Systems (BMS) to monitor detailed three-phase information. Requires one communication slot and optional cables.

3.High Voltage 6 Alarm Relays Card (66069): A second set (one set provided standard with the UPS module) of six (6) normally open dry contact outputs rated at 2.0 A (250 VDC / 30 VDC) shall be available to monitor UPS operation. The dry contacts will close on the conditions listed below, but shall be user programmable to close on preset thresholds of other user UPS parameters:

ƒUPS on Line

ƒLoad on Bypass

ƒUPS on Battery

ƒLow Battery Warning

ƒBattery Fault

ƒGeneral Alarm

Two (2) dry contact inputs shall also be provided to turn the UPS inverter on and off remotely upon closure of the contacts. This feature may also be disabled if required.

4.Network Management Card (66074): The Network Management Card (NMC) shall provide a web interface, SNMP (Simple Network Management Protocol), logging and email capabilities. The NMC shall be used for remote monitoring or graceful shutdown for most popular file servers.

5.IBM AS/400 Volt-Free Contact/Remote Power Off Card (66068): The UPS shall interface with an IBM® AS400-UPS signal interface providing the following signals via dry contacts:

ƒ

ƒ

ƒ

ƒ

load on battery load on bypass

low battery shutdown warning load powered by UPS

6.MultiSlot Communications Card Expander (66071): The MultiSlot shall provide three additional communication slots. The U-Talk Acquisition Card (66063) is included.

C.28” Parallel System Bypass Cabinet (SBC): The System Bypass Cabinet shall be equipped with two manually operated circuit breakers with keyed interlocks for safe operation. The System Bypass Cabinet shall be capable of routing the utility or bypass source completely around up to two UPS modules, and effectively isolating the UPS modules. The bussing shall accommodate landing space for up to two UPS modules and input and out sources of up to 160 or 320kVA depending on model selected. Secondary UPS isolation breakers (2) are standard on the SBC for additional UPS isolation. No Metering at SBC level.

D.42” Parallel System Bypass Cabinet (SBC): The System Bypass Cabinet shall be equipped with two manually operated circuit breakers with keyed interlocks for safe operation. The System Bypass Cabinet shall be capable of routing the utility or bypass source completely around up to six UPS modules, and effectively isolating the UPS modules. The bussing shall accommodate landing space for up to six UPS modules and input and out sources of up to

APC – MGE Galaxy 5000 Specification (60Hz) 12

Effective: June 1, 2008 REV X0 JJG

Parallel Module

 

Image 12
Contents MGE Galaxy General SummaryStandards SubmittalsTemperature Final SubmittalsQualifications & Quality Assurance DELIVERY, STORAGE, and HandlingWarranty Service and Spare PartsMAINTENANCE, Accessibility and Self Diagnostics AC Input Characteristics AC Output CharacteristicsSystem Description UPS Design RequirementsBattery PFC Rectifier and Battery ChargerModes of Operation Component DescriptionInverter Static Bypass 100% Rated, Continuous DutySystem Controls and Indicators Output Static Switch 100% Rated, Continuous DutyMeasurements Status Indications and Events Cabinet Weights and Dimensions The width of the UPS is Mechanical Design and VentilationBattery Optional AccessoriesExternal Control and Communications Devices Page Maintenance Training Maintenance & Service ContractsSpare Parts END of Section Configuration Battery 100 130 KVA 40 KVA 50 KVA 60 KVA 80 KVA 100 130111 150 182 120 156Entry Battery Weight80 KVA 100 KVA 130 KVA 109 137 164 219 273 355300 lbs 700 lbs
Related manuals
Manual 19 pages 13.16 Kb