2.RS232 or RS485 JBus/Modbus Card (66061): The
3.High Voltage 6 Alarm Relays Card (66069): A second set (one set provided standard with the UPS module) of six (6) normally open dry contact outputs rated at 2.0 A (250 VDC / 30 VDC) shall be available to monitor UPS operation. The dry contacts will close on the conditions listed below, but shall be user programmable to close on preset thresholds of other user UPS parameters:
UPS on Line
Load on Bypass
UPS on Battery
Low Battery Warning
Battery Fault
General Alarm
Two (2) dry contact inputs shall also be provided to turn the UPS inverter on and off remotely upon closure of the contacts. This feature may also be disabled if required.
4.Network Management Card (66074): The Network Management Card (NMC) shall provide a web interface, SNMP (Simple Network Management Protocol), logging and email capabilities. The NMC shall be used for remote monitoring or graceful shutdown for most popular file servers.
5.IBM AS/400
load on battery load on bypass
low battery shutdown warning load powered by UPS
6.MultiSlot Communications Card Expander (66071): The MultiSlot shall provide three additional communication slots. The
C.28” Parallel System Bypass Cabinet (SBC): The System Bypass Cabinet shall be equipped with two manually operated circuit breakers with keyed interlocks for safe operation. The System Bypass Cabinet shall be capable of routing the utility or bypass source completely around up to two UPS modules, and effectively isolating the UPS modules. The bussing shall accommodate landing space for up to two UPS modules and input and out sources of up to 160 or 320kVA depending on model selected. Secondary UPS isolation breakers (2) are standard on the SBC for additional UPS isolation. No Metering at SBC level.
D.42” Parallel System Bypass Cabinet (SBC): The System Bypass Cabinet shall be equipped with two manually operated circuit breakers with keyed interlocks for safe operation. The System Bypass Cabinet shall be capable of routing the utility or bypass source completely around up to six UPS modules, and effectively isolating the UPS modules. The bussing shall accommodate landing space for up to six UPS modules and input and out sources of up to
APC – MGE Galaxy 5000 Specification (60Hz) 12 | Effective: June 1, 2008 REV X0 JJG |
Parallel Module |
|