3.2BATTERY

The UPS module shall use a valve regulated sealed lead acid heavy-duty industrial battery, designed for auxiliary power service in a UPS application. The primary battery shall be furnished with impact resistant plastic cases and housed in a matching cabinet(s) next to the UPS module.

A.Protection Against Deep Discharge and Self-Discharge: The UPS shall be equipped with a device designed to protect the battery against deep discharge, depending on discharge conditions, with isolation of the battery by a circuit breaker. In particular, a monitoring device shall adjust the battery shutdown voltage as a function of a discharge coefficient to avoid excessive discharge at less than the rated output. A second device shall avoid self-discharge of the battery into the UPS control circuits during an extended shutdown of the UPS (over two hours).

B.Battery Self-Tests: The battery monitoring system shall be able to perform the following automatic functions:

„Battery circuit checks every twelve hours

„Open-circuit battery test once a month

„Partial discharge test every three months

This self-test system shall signal faults via LEDs on the front panel or a message to remote supervision systems.

4.0OPTIONAL ACCESSORIES

A.Extended Battery Cabinet: Matching battery cabinets shall be furnished in both adjacent or stand alone versions. The cabinet shall match the height and depth of the UPS module and shall have a width of 26”, 36, 48” per battery cabinet. All power wiring and control cables shall be included for adjacent models (remote cabinet cables provided by customer)

B.External Control and Communications Devices

Up to three of the following control and communications devices may be installed in the UPS module:

1.RS232/U-Talk or Dry Contacts Card (66060): The U-Talk protocol shall be used with Solution-Pac 2 for remote monitoring or graceful shutdown for most popular file servers. The dry contacts will close on predefined conditions to monitor UPS operations.

Requires one communication slot and optional cables. The dry contacts will close on the conditions listed below, but shall be user programmable to close on preset thresholds of other user UPS parameters:

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

UPS on Line Load on Bypass UPS on Battery Low Battery Warning Battery Fault General Alarm

Two (2) dry contact inputs shall also be provided to turn the UPS inverter on and off remotely upon closure of the contacts. This feature may also be disabled if required.

APC – MGE Galaxy 5000 Specification (60Hz) 11

Effective: June 1, 2008 REV X0 JJG

Parallel Module

 

Image 11
Contents Submittals MGE GalaxyGeneral Summary StandardsDELIVERY, STORAGE, and Handling TemperatureFinal Submittals Qualifications & Quality AssuranceMAINTENANCE, Accessibility and Self Diagnostics WarrantyService and Spare Parts UPS Design Requirements AC Input CharacteristicsAC Output Characteristics System DescriptionComponent Description BatteryPFC Rectifier and Battery Charger Modes of OperationStatic Bypass 100% Rated, Continuous Duty InverterOutput Static Switch 100% Rated, Continuous Duty System Controls and IndicatorsMeasurements Status Indications and Events Mechanical Design and Ventilation Cabinet Weights and Dimensions The width of the UPS isExternal Control and Communications Devices BatteryOptional Accessories Page Spare Parts Maintenance TrainingMaintenance & Service Contracts END of Section 120 156 Configuration Battery 100 130 KVA40 KVA 50 KVA 60 KVA 80 KVA 100 130 111 150 182109 137 164 219 273 355 Entry BatteryWeight 80 KVA 100 KVA 130 KVA300 lbs 700 lbs