Schneider Electric 5000 specifications Measurements

Page 8

oThe graphic display shall assist the user by providing step by step help in the user's language.

oLED mimic diagram

oThe mimic diagram shall enable display of installation parameters, configuration, operating status and alarms and indication of operator instructions for switching

operations (e.g. bypass).

oIt shall be possible to display the following measurements:

ƒinverter output phase-to-phase voltages;

ƒinverter output currents;

ƒinverter output frequency;

ƒvoltage across battery bank;

ƒbattery charge or discharge current;

ƒrectifier/charger input phase-to-phase voltages;

ƒrectifier/charger input currents;

ƒactive and apparent power;

ƒpower factor of the load;

ƒbattery temperature.

ƒdisplay of status conditions and events

oIt shall be possible to display the following indications:

ƒload on battery power;

ƒload on UPS;

ƒload on automatic bypass;

ƒgeneral alarm;

ƒbattery fault;

ƒremaining battery backup time;

ƒlow battery warning;

ƒbypass AC source outside tolerances;

oAdditional information shall be provided in view of accelerating servicing of the system.

oLog of time-stamped events

ƒThis function shall store in memory and make available, for automatic or manually initiated recall, time-stamped logs of all important status changes, faults and malfunctions, complete with an analysis and display of troubleshooting procedures. It shall be possible to time stamp and store at least 2 000 events.

B.Front Panel LCD Display: The UPS control panel shall provide a back-lit, color graphic display with choice of over 15 operating languages for indication of UPS status, metering, battery status, alarm/event log, and advanced operational features. The display provides access to:

ƒ

ƒ

ƒ

ƒ

ƒ

Mimic diagram indicating UPS power flow Measurements, status indications and events

Personalization menu protected by a password, used to make specific settings Event log with time stamping

Access to all measurements

System Parameters Monitored: The visual display will display the following system parameters based on true RMS metering:

Measurements:

ƒ

ƒ

Input voltage (Ph-Ph) Input current per phase

APC – MGE Galaxy 5000 Specification (60Hz) 8

Effective: June 1, 2008 REV X0 JJG

Parallel Module

 

Image 8
Contents MGE Galaxy General SummaryStandards SubmittalsTemperature Final SubmittalsQualifications & Quality Assurance DELIVERY, STORAGE, and HandlingMAINTENANCE, Accessibility and Self Diagnostics WarrantyService and Spare Parts AC Input Characteristics AC Output CharacteristicsSystem Description UPS Design RequirementsBattery PFC Rectifier and Battery ChargerModes of Operation Component DescriptionInverter Static Bypass 100% Rated, Continuous DutySystem Controls and Indicators Output Static Switch 100% Rated, Continuous DutyMeasurements Status Indications and Events Cabinet Weights and Dimensions The width of the UPS is Mechanical Design and VentilationExternal Control and Communications Devices BatteryOptional Accessories Page Spare Parts Maintenance TrainingMaintenance & Service Contracts END of Section Configuration Battery 100 130 KVA 40 KVA 50 KVA 60 KVA 80 KVA 100 130111 150 182 120 156Entry Battery Weight80 KVA 100 KVA 130 KVA 109 137 164 219 273 355300 lbs 700 lbs