Schneider Electric 5000 specifications Status Indications and Events

Page 9

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

Bypass voltage Bypass input frequency

UPS output voltage (Ph-Ph and Ph-N) UPS output current per phase

UPS output frequency UPS output % load UPS output kVA

UPS output power factor Battery voltage

Crest factor Battery current

Battery backup time and remaining service life

Status Indications and Events:

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

ƒ

Load on battery Load on UPS

Load on automatic bypass Low-battery warning General alarm

Battery fault

Remaining back-up time during operation on battery power Bypass source outside tolerances

Additional indications shall provide maintenance assistance

Time-Stamped Historical Events: This function shall time-stamp and store all important status changes, anomalies and faults and make this information available for automatic or user-requested consultation.

B.LED Status Indicators: The UPS control panel shall provide three LEDs that signal the following status conditions:

ƒ

ƒ

ƒ

Green LED: Load protected

Yellow LED: minor fault

Red LED: major fault, load not protected

C.On/Off Switch: The UPS shall provide the ON and OFF buttons to start and stop the inverter. The switch shall provide a built-in time delay to eliminate the risk of inadvertent operation (additional confirmation is requested). It is possible to remotely activate the OFF function via an isolated dry contact to create an emergency power off function, resulting in:

ƒ

ƒ

ƒ

ƒ

Inverter shutdown

Opening of the automatic bypass

Opening of the input, bypass, output and battery switches/circuit breakers Opening of the isolated dry contact on the programmable relay card

APC – MGE Galaxy 5000 Specification (60Hz) 9

Effective: June 1, 2008 REV X0 JJG

Parallel Module

 

Image 9
Contents General Summary MGE GalaxyStandards SubmittalsFinal Submittals TemperatureQualifications & Quality Assurance DELIVERY, STORAGE, and HandlingWarranty Service and Spare PartsMAINTENANCE, Accessibility and Self Diagnostics AC Output Characteristics AC Input CharacteristicsSystem Description UPS Design RequirementsPFC Rectifier and Battery Charger BatteryModes of Operation Component DescriptionStatic Bypass 100% Rated, Continuous Duty InverterOutput Static Switch 100% Rated, Continuous Duty System Controls and IndicatorsMeasurements Status Indications and Events Mechanical Design and Ventilation Cabinet Weights and Dimensions The width of the UPS isBattery Optional AccessoriesExternal Control and Communications Devices Page Maintenance Training Maintenance & Service ContractsSpare Parts END of Section 40 KVA 50 KVA 60 KVA 80 KVA 100 130 Configuration Battery 100 130 KVA111 150 182 120 156Weight Entry Battery80 KVA 100 KVA 130 KVA 109 137 164 219 273 355300 lbs 700 lbs