Bypass voltage Bypass input frequency
UPS output voltage
UPS output frequency UPS output % load UPS output kVA
UPS output power factor Battery voltage
Crest factor Battery current
Battery backup time and remaining service life
Status Indications and Events:
Load on battery Load on UPS
Load on automatic bypass
Battery fault
Remaining
Additional indications shall provide maintenance assistance
B.LED Status Indicators: The UPS control panel shall provide three LEDs that signal the following status conditions:
Green LED: Load protected
Yellow LED: minor fault
Red LED: major fault, load not protected
C.On/Off Switch: The UPS shall provide the ON and OFF buttons to start and stop the inverter. The switch shall provide a
Inverter shutdown
Opening of the automatic bypass
Opening of the input, bypass, output and battery switches/circuit breakers Opening of the isolated dry contact on the programmable relay card